NOTE:
It is recommended to install an outside air inlet of minimum 4” diameter in the room where the heating appliance is
installed (see drawing below). To do so, it is preferable to choose a wall which is not exposed to extreme winds,
according to the conditions surrounding your house.
N.B. The owner of the furnace is responsible for the room salubrity in case of negative pressure or temporary
negative pressure.
ELECTRICAL CONNECTION
The following instructions do not supersede the local code.
WOOD ONLY
Install the fan limit control on the support provided after securing this support on the left edge of the hot air plenum
where two holes are pre-drilled (
there are four pre-drilled holes on the edge of the PSG3000, use the two that are
located farther
back
). Install the servo-motor on the facade above the door, on the right side (use pre-drilled holes).
The chain that links the air inlet latch to the motor must have a play of 1/8 in. When there is no call for heat, the air
inlet latch must be completely shut and the chain must be affixed to the servo-motor at “8 o’clock”.
*
The red switch located on the junction box controls low speed operation of the blower, in either ON (continuous
operation) or OFF modes.
WARNING: USE FEEDING WIRES SUITABLE FOR 75
O
C
WOOD/ELECTRIC
The high limit control on the electric unit is a manual reset thermostatic captor that is located directly inside the
electric unit
(see INSIDE VIEW OF THE ELECTRIC ELEMENT
). The electric elements must be installed as shown on
the diagram. Install the wood combined fan limit control on the support provided, at the determined location. The
connections must conform to the diagram.
Install the servo-motor on the facade above the door, on the right side (use pre-drilled holes). The chain that links
the air inlet latch to the motor must have a play of 1/8 in. When there is no call for heat, the air inlet latch must be
completely shut and the chain must be affixed to the servo-motor at “8 o’clock”.
*
WARNING: USE FEEDING WIRES SUITABLE FOR 75
O
C
*
(With all reserves on the minimum combustion air to be increased depending on the type and quality of the
combustible).
Insulated conduit full lenght
Fresh air
intake
Exterior
wall
Free air
entry