19
MINI-CADDY ADD-ON
3.1.6 BLOWER OF THE EXISTING FURNACE
The blower of the existing furnace shall produce an average air flow in the
plenum in between 750 to 1,250 cfm when the external static pressure is
adjusted to 0,2" of water column and in between 650 to 1100 cfm when adjusted
to 0,5" of water column.
Some adjustment on the motor and blower of the existing furnace may be
necessary. In this case, the following rules apply:
On a belt-driven system, blower pulleys and motor pulleys may be changed to
do the adjustment.
On a direct-drive system, the motor shall not be changed; however, the speed
of the motor may be increased or decreased.
CAUTION
THE BLOWER OF THE EXISTING FURNACE ITSELF SHALL NOT BE
CHANGED.
WARNING
THE ELECTRICAL CURRENT FLOWING THROUGH THE BLOWER MOTOR
SHALL NOT EXCEED THE NAMEPLATE RATING.
3.1.7 MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS FOR MINI-
CADDY ADD-ON
N.B.: THIS APPLIANCE MUST BE INSTALLED IN ACCORDANCE WITH THE
INSTRUCTIONS ON THE CERTIFICATION PLATE APPLIED ON THE UNIT.
Содержание MINI-CADDY PF01301
Страница 15: ...15 MINI CADDY ADD ON Installation Instructions MINI CADDY ADD ON PF01301 ...
Страница 25: ...25 MINI CADDY ADD ON Example 1 Example 2 ...
Страница 34: ...34 MINI CADDY WOOD ONLY Installation instructions for MINI CADDY WOOD ONLY PF01301 ...
Страница 41: ...41 MINI CADDY WOOD ONLY 3 2 13 WIRING DIAGRAM ...
Страница 43: ...43 MINI CADDY WOOD ELECTRIC Installation instructions for MINI CADDY WOOD ELECTRIC PF01301 ...
Страница 48: ...48 MINI CADDY WOOD ELECTRIC 3 3 7 WIRING DIAGRAM ...