31
4.5.2 System
Balancing
It is important to call upon a professional installer for the installation of the furnace and the ducting system
configuration. Certain check-ups must be performed and certain rules must be respected in order not to damage the
blower. When all components are installed on the furnace and the ducting system is connected to the various rooms
of the house, you must balance the ducting system. In order to do so, start the furnace blower by selecting the
recirculation mode (CIRC). Then, in the FAN section, use the arrows to select speed #4 (refer to Table 2). It is
important to respect the velocity in the main duct, the secondary ducts, as well as the velocity at the room outlets.
The static pressure of your system must be adjusted to at least 0.2 IN.W.C. and must not exceed 0.5 IN.W.C.
Finally, make sure that you never exceed the maximum blower motor full load amperage.
4.5.3 HEAT Mode (automatic heating)
Operation
When the temperature in your house is below the value at which your wall thermostat is programmed, a signal is
sent to your furnace through the PC board, activating the motorized damper located in front of the furnace and thus
allowing more oxygen to the fire. The RTD temperature probe, located inside the hot air plenum of your furnace,
reads the plenum temperature continuously. When the temperature reaches the start-up value selected by the user
(KIP –
Kick-in Point
), the distribution blower starts functioning at the minimum speed. Thereafter, the blower
increments its speed until it reaches the best efficiency point (BEP) determined by the manufacturer. If the
temperature inside the hot air plenum exceeds the limit determined by the manufacturer, the blower automatically
selects the maximal speed and the motorized damper closes in order to slow down combustion. When the
temperature returns to a safe level, the blower speed gradually returns to the speed required to maintain the BEP.
Programming
Make sure that your wall thermostat is well connected to the PC board. Make sure that the right port has been
selected based on the type of thermostat (e.g. 24VAC or Millivolt).
In the MODE menu, select HEAT by pushing the SELECT button. Then, using the arrows buttons, choose from the
different selections: KIP, TEMP, or UNIT. Consult the “
Selections
” section in order to obtain a complete definition
of the terms KIP, TEMP, and UNIT.
When your choice is made, press SELECT. Then, use the arrows to make the appropriate adjustment. Press
SELECT to memorize your adjustment. To change the selection ( KIP, TEMP, or UNIT) push an arrow button. To
go back to the main menu (HEAT, COOL, CIRC, MANU), push on the MODE button. After two minutes of inactivity
on the keyboard, the display will shut itself off.
4.5.4 COOL Mode (air conditioning)
Operation
If an air conditioning unit is installed, the PC board will have to be connected to a dual-function wall thermostat (e.g.
“heat/cool”) in order to synchronize the start of the furnace blower with the start of the air conditioning condenser.
Upon receiving the wall thermostat’s signal, the furnace blower will start functioning at the speed selected by the
user.
Programming
Make sure that your wall thermostat is well connected to the PC board. Make sure that the right port has been
selected based on the type of thermostat (e.g. 24VAC or Millivolt).
In the MODE menu, select COOL by pushing the SELECT button. Then, using the arrows buttons, choose from the
different selections: TEMP, UNIT, or FAN. Consult the “
Selections
” section in order to obtain a compete definition
of the terms TEMP, UNIT, and FAN.
When your choice is made, press SELECT. Then, use the arrows to make the appropriate adjustment. Press
SELECT to memorize your adjustment. To change the selection (TEMP, UNIT, or FAN) push an arrow button. To
go back to the main menu (HEAT, COOL, CIRC, MANU), push on the MODE button. After two minutes of inactivity
on the keyboard, the display will shut itself off.
Содержание MAX CADDY PF01101
Страница 38: ...38 7 GENERAL ELECTRIC DIAGRAM WITH BECKETT OIL BURNER ...
Страница 39: ...39 8 GENERAL ELECTRIC DIAGRAM WITH RIELLO OIL BURNER ...
Страница 40: ...40 9 ELECTRIC DIAGRAM WITH OPTIONAL ELECTRICAL ELEMENT MAX CADDY WOOD ELECTRIC COMBINATION FURNACE ...
Страница 42: ...42 ...
Страница 45: ......
Страница 54: ...54 EXPLODED DIAGRAM AND PARTS LIST ...