30
15.9. FLOOR PROTECTION
If the floor is made of non-combustible material, no
floor protector is required.
If the floor is made of combustible material, a non-
combustible material floor protector is required (see
table below).
FLOOR PROTECTION*
CANADA
A
18" (457 mm)
From door opening
C
8" (203 mm)
D
8" (203 mm)
– Note 1
*Steel with a minimum thickness of 0.015" (0.38 mm) or ceramic tiles sealed together with grout. No protection is required if the unit
is installed on a non-combustible floor (ex: concrete).
Note 1: The floor protection at the back of the add-on is limited to the add-on required clearance (A) if such clearance is smaller
than 8 inches (203 mm).