PSB Model ET-4 NEMA 4 & ET-5 NEMA 4  - Automatic Timer/Drain Valves 

Toggle Switch Settings – Switches Are Mounted On The Printed Circuit 
Board, Under The Top Cover. 
 

“X” indicates the switch is on. 
 

Time Between Valve Openings 

Time Valve Is Open 

 

SWITCH NUMBERS 

 

 
Hrs./Min. 

  2 

   4 

Seconds 

     8       

:15 
:30 
:45

 

 

 
   

X –Factory Setting

  

   X 

 

4.5 
9.0 

13.5 

 

 
   

X—Factory Setting 

   X 

 

1:00 
1:15 
1:30 

 

 

 
 



 

18.0 
22.5 
27.0 

 

 
 

 X 


1:45 
2:00 
2:15 

 

X X 

 
  X 
  X 

31.5 
36.0 
40.5 

 

X  


2:30 
2:45 
3:00 

 


 
 

  X 
  X 
  X 

45.0 
49.5 
54.9 

 




 
 

3:15 
3:30 
3:45 

 

 




  X 
  X 
  X 

58.5 
63.0 
67.5 

 

 






 
 
 
Valve can be set for time between openings with any valve time open. 

 

Power supply 120 volt single phase. 
 
To change times, remove six socket head cap screws, lift off cover and reset 
switches as required. 
 
To check proper functioning of the printed circuit board and to manually operate 
valve, press and release manual override on side of housing.  Valve will open and 
remain open for the set opening time.  Valve will then close and timer will start a 
new cycle. 
 
If the manual override is pressed and valve does not turn, the circuit board may be 
defective and should be replaced or repaired at the factory. 
 
 
 