13
• When alarms are interconnected, all interconnected units must be powered from a single circuit.
• A maximum of 24
PSA
LIFESAVER devices may be interconnected in a multiple station arrangement.
Note: Use approved listed Australian Standards cable 1.0mm² TPS or larger as required by
local codes.
FIGURE 5 “INTERCONNECT WIRING DIAGRAM”
ALARM HARNESS ------------------------ CONNECTED TO:
RED -------------------------- A (Hot Side of AC Line)
BLACK ----------------------- N (Neutral Side of AC Line)
WHITE ---------------------- SW (Interconnect Lines (Red
Wires) of Other Units in the
Multiple Station Set up)
FIGURE 5
A
N
FUSE OR CIRCUIT BREAKER
RED
WHITE
BLACK
A
SW
N
RED
WHITE
BLACK
A
SW
N
RED
WHITE
BLACK
A
SW
N
RED
WHITE
BLACK
LIFESAVER
INTERCONNECT
SMOKE
ALARM
LIFESAVER
INTERCONNECT
CO
ALARM
LIFESAVER
INTERCONNECT
HEAT
ALARM
L O W
BA TTE R Y
POW E R
FL A SH I N G
= AL A R M
1
Fl a s h
= SER V I CE