Mounting Panel
Selecting Transformer
Installing Dampers
Wiring Dampers
Remove the top cover and attach the panel to a wall close to
the unit using four #8 screws.
The VA rating of the transformer depends on the number of
actuators being used. The table below shows the VA required
for each zoning component including the ProR80J dampers.
One or more dampers can be used to define a zone. Dampers
should be installed in the duct or ducts and sealed to insure no
air leakage. Shown below is the ProR80J-XX damper.
The dampers are connected to the zoning panel with the cables
provided with each damper.
The table below shows the number of dampers that can be
used with a 3 -zone installation using a 40, 60 or 75VA
transformer and ProR80J dampers.
Install the 24VAC transformer according to local electrical
codes and connect the 24VAC output to the terminals on the
panel using 2-conductor, 18 gage, thermostat wire as shown
below.
1.
2.
3.
4.
HVAC
PANEL
ZONE DAMPERS
1
1
2
2
3
FAD
3
THERMOST
ATS
Q
u
ic
k
V
ie
w
ProC332J Zoning Panel
ProZone
Two #8 screws
Two #8 screws
Panel
3-Zone
Maximum VA
40VA Transformer 60VA Transformer 75VA Transformer
10VA
11 Dampers
19 Dampers
26 Dampers
1.8VA
2.4VA
Typical VA
10VA
1.0VA
1.0VA
Zone Thermostat
Zone Damper
Line
24VAC
2-conductor, 18 gage
Thermostat Wire
Zoning Panel
25-foot RJ12 cable
supplied with damper.
Plug damper cable into the
Zone Damper connector on
the zoning panel.
Daisy chained dampers
when more than one
damper required to
configure a zone.