The non-calling zone dampers can be opened just enough to 
keep the airflow in the calling zones from being too high or noisy.  
The PDMi3 can be used set the bypass position for each zone in 
heating and cooling during installation.

When non-calling zone dampers are used for bypass, the amount 
of bypass can be set for each zone being used in heating and 
cooling.

Although both the calling and non-calling zones are receiving 
conditioned airflow, the calling zone is being conditioned typically 
3-4 times faster than the non-calling zones.

Increase the bypass positions.

Decrease the bypass positions.

Bypass Using the Non-Calling Zone Dampers

Selecting the Bypass Option

To Reduce the Airflow into the Calling Zones

To Reduce the Airflow into the Non-Calling Zones

Press Yes to change the Bypass options 
or press No to continue to next menu 
selection.

Press Yes if bypass is controlled by a 
bypass duct and barometric damper or 
using the Close stop position on the 
actuators. Or press No to display other 
bypass options.

Press Yes if bypass is achieved using the 
non-calling zone dampers. Or press No 
to return to the first option.

Press Up or Down to adjust the bypass 
position of the damper when it is being 
used for bypass. Press Next to set the 
bypass position of the next damper.

Press Up or Down to adjust the bypass 
position of the damper when it is being 
used for bypass. Press Next to set the 
bypass position of the next damper.

Press Up or Down to adjust the bypass 
position of the damper when it is being 
used for bypass. Press Next to set the 
bypass position of the next damper.

Press Up or Down to adjust the bypass 
position of the damper when it is being 
used for bypass. Press Next to set the 
bypass position of the next damper.

Press Up or Down to adjust the bypass 
position of the damper when it is being 
used for bypass. Press Next to set the 
bypass position of the next damper.

Press Up or Down to adjust the bypass 
position of the damper when it is being 
used for bypass. Press Next to display 
the next menu selection.

Change Bypass
Options      Y/N

Bypass  Ext Baro
             Y/N

Bypass ZoneDmprs
             Y/N

Zone1 Htg    50%
BP Pos  U/D/NEXT

Zone1 Clg    50%
BP Pos  U/D/NEXT

Zone2 Htg    50%
BP Pos  U/D/NEXT

Zone2 Clg    50%
BP Pos  U/D/NEXT

Zone3 Htg    50%
BP Pos  U/D/NEXT

Zone3 Clg    50%
BP Pos  U/D/NEXT

Staging is controlled by the number of zones calling for heating or 
cooling and by a timer that monitors the amount of time a call has 
been active.  Each stage can be set to activate based on the total 
of the weighted zones calling or set to only be activated by the 
timer. 

Title24 now requires delaying auxiliary electric strip heating in a 
heat pump so it does not activate on a recovery from a setback 
temperature.  The stage used for auxiliary heat can be set to 
activate only by the timer.

Staging is controlled by the number of zones calling for 
heating or cooling.

Staging Heating and Cooling Calls

Staging Based on Zone Calls

Press Yes to change the staging of 
heating and cooling calls or press No to 
continue to next menu selection.

Press Yes to select staging based on the 
number of zones calling or press No to 
display other staging options.

Press Yes to select staging based on 
the number of zones calling.

Press Up or Down to set the 
weighted zones required to activate a 
Stage1 call.  In installations with three 
or more zones and one small zone, 
the limit can be set above the small 
zone’s size to prevent it, alone, from 
activating a call and have excessive 
bypass.  Press NEXT to continue.

Press Up or Down to set the 
weighted zones required to activate a 
Stage2 call.  Press NEXT to continue.

Press Up or Down to set the 
weighted zones required to activate a 
Stage3 call.  Holding Up, the limit will 
increase to the maximum value (3.0 
for a 3-zone panel) and then display 
“Tmr” to indicate this staging is 
controlled by the staging timer and 
not the weighted zones calling.  
Press NEXT to continue to the next 
menu.

Press Yes to select timed upstaging or 
press No to display other staging 
options.

Press Yes to select limiting upstaging 
based on outdoor temperature or press 
No to display the first staging option.

Change Staging
             Y/N

Limit Staging By
Zones        Y/N

Limit Staging By
Zones        Y/N

Stage 1 Lmt  1.0
Zones   U/D/NEXT

Stage 2 Lmt  3.0
Zones   U/D/NEXT

Stage 3 Lmt  Tmr
Zones   U/D/NEXT

Timed
UpStaging    Y/N

Limit Staging
OD Temp      Y/N

11

Содержание ProC232J

Страница 1: ...umps Selected using the PDMi3 plug in programming display module See table below See table below See table below HVAC PANEL ZONE DAMPERS 1 1 2 2 3 Fresh Air 3 THERMOSTATS Quick View Zoning Panel ProZo...

Страница 2: ...the plenum or freezing the indoor coil Color coded terminals for heat cool or heat pump thermostat Thermostat type selected using the PDMi3 Use 24VAC powered or battery powered thermostats VAC termina...

Страница 3: ...stall the 24VAC transformer according to local electrical codes and connect the 24VAC output to the terminals on the panel using 2 conductor 18 gage thermostat wire as shown below 1 2 3 4 HVAC PANEL Z...

Страница 4: ...heat pump thermostat should be used in Zone1 when heat pump equipment is selected Wiring of a heat pump zone thermostat is shown below Thermostat R C OB W2 E Y1 G Zoning Panel Terminal Function 24VAC...

Страница 5: ...the red and white thermostat wires to the thermistor wires no polarity using the wirenuts 3 Push the wirenuts and wire into the cover and secure the cover with the screw 1 Connect the red and white th...

Страница 6: ...respond to the Zone1 thermostat When the occupant leaves the home they can set the switch to Vacant and only set the Zone1 thermostat Installing the Duct Pressure Sensor Drill a 3 8 inch diameter hol...

Страница 7: ...es or navigate Press the CANCEL to cancel settings and return to the main menu The panel is ready to operate and control the equipment selected The PDMi3 can be used to customize the panel clone it fr...

Страница 8: ...s Yes to set the number of stages of heating and cooling the fan operation the supply air temperature limits outdoor changeover temperature for dual fuel heat pumps and number of zones being used Pres...

Страница 9: ...T Aux Heating 1 Stages U D NEXT Fan Mode Gas N NEXT Htg Temp Lmt 160 U D NEXT Htg Temp Lmt 160 U D NEXT Clg Temp Lmt 45 U D NEXT Clg Temp Lmt 45 U D NEXT Total Zones 3 Used U D NEXT Total Zones 3 Used...

Страница 10: ...heat cool thermostat for that zone Press No to see other thermostats that can be used in that zone Press Up or Down to change the number of auxiliary heating stages Press NEXT to continue If a heat pu...

Страница 11: ...Y N Bypass Ext Baro Y N Bypass ZoneDmprs Y N Zone1 Htg 50 BP Pos U D NEXT Zone1 Clg 50 BP Pos U D NEXT Zone2 Htg 50 BP Pos U D NEXT Zone2 Clg 50 BP Pos U D NEXT Zone3 Htg 50 BP Pos U D NEXT Zone3 Clg...

Страница 12: ...N Fresh Air Off Y On N Off If the contractor has calculated the CFM for fresh air and sized the damper to operate for a number of minutes each hour the minutes can be directly entered The PDMi3 allows...

Страница 13: ...Down to set the weighted zones when low speed fan is activated In the example if the weighted demand is less than 2 0 DSBK is activated Press Next to continue to next menu selection Press Yes to selec...

Страница 14: ...ooling stage Press Yes to start a test of the heating system to insure discharge temperature is correct Press Next to start a test stage2 heating to insure discharge temperature is correct or return t...

Страница 15: ...select the letter or number Press NEXT to go to the next letter in the name Press SAVE to save the clone name Monitor HVAC Performance Y N LAT 122 Prs 0 55 BP Pos 35 NEXT Press Yes to display the leav...

Страница 16: ...una Hills CA 92653 949 916 0945 Fax 949 458 8502 www ProZone US com Limited 5 Year Warranty The 5 year warranty is limited to the repair or replacement of defective product due to parts failure or def...

Отзывы: