Microcontroller-controlled temperature difference controller for solar thermal systems

Operating manual

Solareg II ENERGY

Содержание Solareg II ENERGY

Страница 1: ...Microcontroller controlled temperature difference controller for solar thermal systems Operatingmanual Solareg II ENERGY...

Страница 2: ...7 1 4 Tube collector or start function 11 7 2 Protective functions 11 7 2 1 Collector protection 11 7 2 2 Recooling Holiday function 11 7 2 3 System protection 12 7 3 Additional function 12 7 3 1 Ene...

Страница 3: ...ection recooling and flow monitoring Generous wiring space Available accessories Temperature sensor PT1000 Yield measurement set incl tube sensor Sensor connection box Immersion sleeves 2 Safety instr...

Страница 4: ...opened 3 2 Wall mounting The device is mounted on the marked points A drilling template is provided with the device Insert the Quick Info card provided with the device into the pocket provided on the...

Страница 5: ...ors 2 sensors are required the third sensor is optional Mounting wiring the temperature sensors Mount the sensors on the collector and the storage tank Ensure proper heat transfer and use heat conduct...

Страница 6: ...decreases continuously Scroll right Select Confirm Scroll right in the main menu Select a menu item Confirm a value change and store it 5 Menu structure 5 1 Info menu The following measured and yield...

Страница 7: ...fer ence 2 35K 3K min 100 12 Set the minimum pump capacity using the RPM control 100 RPM control off 30 100 100 40 C Switch on tem perature for the thermostat func tion 20 90 C 40 C dT 10 K Hysteresis...

Страница 8: ...f 1 On 0 Off 1 120 C Collector protection function 110 150 C 120 C 2 0 Recooling function only if the collector protection is on 0 Off 1 On 0 Off 3 40 C Recooling temperature 30 90 C 40 C 4 0 Tube col...

Страница 9: ...30V connections L Mains phase N Neutral conductor mains and outputs A1 Solar circuit pump switching output 1 A2 Switching output 2 Sensor connections S1 Collector sensor S2 Lower storage tank S3 Therm...

Страница 10: ...s place when under the preset temperature Basic Setup menu Display Meaning Value range Factory set ting Line Value 6 1 The cooling or thermostat function can also be selected 0 Off 1 Cooling 2 Heating...

Страница 11: ...ecooling Holiday function The collector protection function is only effective if the storage tank temperature is below the temperature limit 95 Therefore during the holiday period for exam ple the sto...

Страница 12: ...enu Display Meaning Value range Factory set ting Line Value 5 0 Switches on or off the energy yield measurement function 0 Off 1 On 0 Off 8 System monitoring If an error occurs the flashing symbol is...

Страница 13: ...ce sensor if necessary Flashing Short circuit in the sensor cable Check cable Defective sensor Check sensor resistance and replace sensor if nec essary Circulation error No flow Flashing Additional di...

Страница 14: ...ircuits Defect device Contact the supplier Outputs are not switched on Controller is in manual operation Exit Manual operation Switch on condition is not satisfied Wait until switch on condition is sa...

Страница 15: ...min according to EN 60730 DIN VDE 0631 IEC 60664 IEC Output Voltage Power switching output 230V 1A approx 230VAfor cos 0 7 1 0 Fuse protection Fine wire fuse 5 x 20mm 2A T 2 amperes delayed action fus...

Страница 16: ...eduction of price is excluded Warranty claims may only be submitted by the customer and are non transferable If a defect occurs during the warranty period please contact the supplier installer When re...