4.0 Reader Specifications
Model
Operating Voltage
Current Rating
Operating Temp.
Proxy Reader Pro //
PRXY-MW-1.0 //
PRXY-MK-1.0
HF LF BLE IEEE
802.11b/g/n
6V - 16V DC
0.5A
-35C to +66C , 85% RH
There shall be no connections made to the RS-485 interface ( RS485+ and RS485-) for
UL installations
Note
:
- Standby Power is not provided by the Card Readers. The Standby Power Level is
dependent on the external power source connected to the Card Reader.
- For RS485 use 24 AWG twisted pair cable with a shunt capacitance of 16 pF per foot
and 100 ohm characteristic impedance (option: Category 5 shielded twisted pair (STP))
4.1 Rated current at different operating voltages
4.1.1 Rated current for PRXY-MW-1.0 & PRXY-MK-1.0
- All wiring or cables to the Card Readers shall be the shielded type.
Voltage (V)
Average Current (mA)
Peak Current (mA)
6
180
260
8
162
248
10
126
200
12
102
165
14
95
135
16
80
125