7
Scheme 2а:
R1
TS1>TS3+dTSol
TS3<Max Tank; TS2<Max Tank; TS1> MinSol
All modes
R1
TS1< DefrSol
TS3>10’C
All modes
R2
TS2< MinTank
R1 was not activated longer than ActSolar value
Auto
R2
TS2< GoodTnk
During preset time interval (time zone)
Auto
R2
TS2< GoodTnk
On
R2
TS2< 5’C
Off/Vakc
R3
TS2> MaxTank
All modes
Scheme 3; 3а:
R1
TS1>TS2+dTSol
TS2< TankA/B; TS1> MinSol
All modes
R1
TS1< DefrSol
TS2>10’C
All modes
R1
TS1>TS3+dTSol
TS2> TankA/B; TS1> MinSol; TS3< Max Tank
All modes
R2
TS2< MinTank
R1 was not activated longer than ActSolar value
Auto
R2
TS2< GoodTnk
During preset time interval (time zone)
Auto
R2
TS2< GoodTnk
On
R2
TS2< 5’C
Off/Vakc
R3
TS2> TankA/B
TS2> TankA/B; TS3> TankA/B; TS3<TS2
TS2 < GoodTnk & LimTnkB=ON
All modes
Scheme 4:
R1
TS1>TS2+dTSol
TS2< Max Tank; TS1> MinSol
All modes
R1
TS1< DefrSol
TS2>10’C
All modes
R2
TS2< MinTank
R1 was not activated longer than ActSolar value
Auto
R2
TS2< GoodTnk
During preset time interval (time zone)
Auto
R2
TS2< GoodTnk
On
R2
TS2< 5’C
Off/Vakc
R3
TS3> TS2+dTKot
TS3> MinKot; TS2< GoodTnk
All modes
R3
TS2> Max Tank
TS3<90’C
All modes
Scheme 5:
R1
TS1>TS2+dTSol
TS2< Max Tank; TS1> MinSol
All modes
R1
TS1< DefrSol
TS2>10’C
All modes
R2
TS3> CH Pump
All modes
R2
TS2> Max Tank
TS3<90’C
All modes
R3
TS3> TS2+dTKot
TS3> MinKot; TS2< GoodTnk
All modes
R3
TS2> Max Tank
TS3<90’C
All modes
Scheme 6:
R1
TS1>TS2+dTSol
TS2< Max Tank; TS1> MinSol
All modes
R1
TS1< DefrSol
TS2>10’C
All modes
R2
TS2 или TS3 < MinTank R1 was not activated longer than ActSolar value
Auto
R2
TS2&TS3< GoodTnk
During preset time interval (time zone)
Auto
R2
TS2&TS3< GoodTnk
On
R2
TS2&TS3< 5’C
Off/Vakc
R3
TS3> TS2+dTКot
TS2> Max Tank; TS1>MinSol
All modes
R3
TS1< DefrSol
TS3>10’C
All modes
Scheme 7:
R1
TS1>TS3+dTSol
TS2<Max Tank; TS1> MinSol
All modes
R1
TS1< DefrSol
TS2>10’C
All modes
R2
TS2< MinTank
R1 was not activated longer than ActSolar value
Auto
R2
TS2< GoodTnk
During preset time interval (time zone)
Auto
R2
TS2< GoodTnk
On
R2
TS2< 5’C
Off/Vakc
R3
Level sensor
TS2<70’С
All modes
8
WARRANTY THERMS AND CONDITIONS:
The warranty period of the product is 24 months from the day of sale or installation by the installer but no more
than 30 months from the date of manufacture. The warranty covers defects attributable to the manufacturer
(manufacturing defects or defective materials). They are not subject to warranty defects in the product or damage to
other equipment as a result of improper or unskilled installation, improper workflow selection and / or adjustment,
unauthorized change of the product, natural disasters, non-standard power supply, improper storage or
transportation.
Warranty card
Please completely fill this card for valid guarantee
Manufacturer: Proxel Engineering Ltd Type: Temperature controller DTSF 3+
Plovdiv, Bulgaria, [email protected]
Serial number: Data of manufacture:
............................. .................................
Seller/Installer:.............................................................................................................................
.
Address: ........................................................................................................................................
Date of (sale) Instalation: .........................................................................................
Installer/ seller :.........................................................................................................
(name and signature )
Instalation is made by
Installer
Client
(please mark the true one)
2004/108/EC
200
6
/
95
/EC