---------- PROXEL ENGINEERING ---------------- www.proxel-bg.com-------------------------------- 3WMREG rev. 2.4 /02.2017------      
 

 

          

 

 

PulseDur 
[3.5sec]6

 

Ext T L 
[-25ºC]11  

 
[10sec] 8

 

ON<>OFF 
[ 60sec]7

 

Period- 
[10sec] 9

 

Passwrd 
[00]   10

 

Ext T M 
[ 0 ºC]12  

Ext T H 
[ 25ºC]13  

Window/Screen #6 –Duration of output pulse for fine adjustment

  

Row 1

: Displays the selected parameter “PulseDur” 

 

Row 2

: The value of the parameter. Range 0.5 ÷ 5.0sek.   

Screen [6] .

 

 

* to change this parameter a password is required

 

 

 
Window/Screen #7  - Total Time to fully open / close the actuator.

  

Row 1

: Displays the selected parameter “ON<>OFF” 

Row 2

: The value of the parameter. Range 15÷250sec.  

Screen [7] 

.

 

* to change this parameter a password is required

 

 

16.

 

Window/Screen #8  - 

Period of applying signal pulse for direction “open”

 

Row 1

: Displays the selected parameter “”  

 

Ред 2

: The value of the parameter. Range 10 ÷ 60sec. 

Screen [8]

 .

 

* to change this parameter a password is required

 

 

 

17.

 

Window/Screen #9  - 

Period of applying signal pulse for direction “close”

 

Row 1

: Displays the selected parameter “Period-”  

 

Row 2

: The value of the parameter. Range 10 ÷ 60sec. 

Screen [9] .

 

* to change this parameter a password is required

 

 

 
Window/Screen #10  - Password field to access protected parameters.

  

Row 1

: Displays the selected parameter “Passwrd”. 

Screen [10]

 

 

Row 2

: Set password.      

Enter the required password to access the protected parameters.  

 

Window/Screen  #11   

Lower  point  of  ambient  temperature  to  describe  the  temperature 

curve (corresponds to "FluidHi")  
Row 1

: Displays the selected parameter “Ext T L” 

 

Row 2

: The value of the parameter. Range -35ºC ÷ “Ext T M-1” ºC. 

Screen [11]

 

 

* to change this parameter a password is required

 

** the parameter is only visible only if operation mode is  ambient temperature correction 

 

 

Window/Screen  #12    -  Middle  point  of  ambient  temperature  to  describe  the  temperature 
curve (corresponds to average of "FluidLo and FluidHi")  

Row 1

: Displays the selected parameter “Ext T M” 

 

Row 2

: The value of the parameter. Range “Ext T L+1” ºC ÷ “Ext T H-1” ºC. 

Screen 

[12] .

 

 * to change this parameter a password is required

 

** the parameter is only visible only if operation mode is  ambient temperature correction 

 
 

Window/Screen  #13  –  Middle  point  of  ambient  temperature  to  describe  the  temperature 
curve (corresponds to of

 “

FluidLo”)

 

Row 1

: Displays the selected parameter “Ext T H” 

 

Row 2

: The value of the parameter. Range “Ext T M-1” ºC ÷ 60 ºC. 

Screen [13]

  

* to change this parameter a password is required

 

** the parameter is only visible only if operation mode is  ambient temperature correction 

 
 
 
 
 
 
 
 
 
 

---------- PROXEL ENGINEERING ---------------- www.proxel-bg.com-------------------------------- 3WMREG rev. 2.4 /02.2017------      
 

 

          

 

 

[Setp

ºC

]  

:ExtTemp

 

02f90278 
03ff

 

FluidLo 
[ 40ºC]14  

FluidHi 
[ 85ºC]15  

CorrFlu 
[  0ºC]16  

[Setp

ºC

]  

:Local T

 

Window/Screen #14 – Minimum temperature of the fluid to describe the temperature curve. 

(corresponds to "ExtT H")

  

Row 1

: Displays the selected parameter “Fluid Lo” 

 

Row 2

: The value of the parameter. Range -10ºC÷“Fluid Lo”+3 ºC. 

Screen [14]

 

* to change this parameter a password is required

 

** the parameter is only visible only if operation mode is  ambient temperature correction 

 
 

Window/Screen #15 – Maximum temperature of the fluid to describe the temperature curve. 

(corresponds to "Ext T L")

  

Row 1

: Displays the selected parameter “Fluid Ho” 

 

Row 2

: The value of the parameter. Range “Fluid Lo”+3÷90ºC.  

Screen [15]

 

 

* to change this parameter a password is required

 

** the parameter is only visible only if operation mode is  ambient temperature correction 

 
 

Window/Screen  #16  –  Temperature  correction  FluidLo  and  FluidHi  "total.  (fast  and 
simultaneous increase / decrease together of temperatures 

Row 1

: Displays the selected parameter "CorrFlu" 

 

Row 2

: The value of the parameter. Range -5ºC ÷ + 5ºC. 

Screen [16]

 

 

* to change this parameter a password is required

 

** the parameter is only visible only if operation mode is  ambient temperature correction 

 
Window/Screen  #17    -  Selection  of  the  working  circuit  (with  or  without  compensation  for 
ambient temperature). 

  Set the operational mode 

 

Row 1

: Displays the selected parameter “Setp

°

C”.   

Row 2

: The selected scheme of work –Sch.1=“:ExtTemp”, Sch.2=”:Local T”,  

Attention! For the correct operation of the device, observe the correct setting of the 
controller operating diagram

  

 

* to change this parameter a password is required

 

 

 

Window/Screen #18  - Calibration of temperature inputs (service mode).

 

 

 
 

 
 

Temperature curve  

 

 

 

 