---------- PROXEL ENGINEERING ---------------- www.proxel-bg.com-------------------------------- 3WMREG rev. 2.4 /02.2017------      
 

 

          

 

 

B:XX  ZZ 
= YYºC WW

 

10.

 

„EXT.T.L”     – Lower point of ambient temperature 

11.

 

„EXT.T.М”    – Middle point of ambient temperature 

12.

 

„EXT.T.H”     – Highest point of ambient temperature 

13.

 

„Fluid Lo”      – Lower possible temperature of fluid 

14.

 

„Fluid Hi”      –  Highest possible temperature of fluid 

15.

 

„FluidCorr”    – General correction of fluid temperature setting

 

 

Others:  

Fixed hysteresis 2 ºC 

Fault notification - entire screen blinking 

Visualization of R1 and R2 
operation      

Manual open / close

 

Important parameter change is password protected 

 

 
USAGE

 

Front pannel 

 

 

     

 

Description

 

- two lines

 

display  

- 3x push buttons:  for Up 

„Up↑”

, for Down 

„Dn↓”, 

to select 

Set

”   

- Push button for selection of operation mode (stop/ automatic)

    

 

- Indicaton of alarm event – blinking of backlight (if a sensor is 

defective)

 

Usage of buttons:

 

1.

 

button 

„Up- ↑”/„Dn-↓”

, navigates among list of parameter screens previous/next; 

activation with holding button "Set" increase / decrease selected value with 1 

2.

 

button „

Set

” change value of selected parameter 

 

3.

 

button „

AUTO/STOP-

” – selects the operational mode of the unit  „AUTO”/ „STOP”

 

 
Available windows and usage 
 
Window #1  - Main window 

 

Displays temperature reading of sensors and operational mode of outputs. 

Row 1

: Outgoing water temperature "

XX", "ZZ

" relative valve status in percent.    

            If there is no sensor - „

no

” is displayed, if sensor is shor circuit or 

resistance - “

sc

” is displayed. 

 

Row  2

:  temperature  set  point  "

YY

",  "

WW

"  ambient  temperature  when  operating  in  ambient 

temperature correction mode  
 
Meaning of symbols:  
”  

+  

”  - When submitting the “opening” command, the sign "=" is changed to "+"  

 ” 

-   

”  - When submitting the "close" command, the sign "=" is changed with "-"  

„ 

”  -  If  the  maximum  movement  is  exceeded in  the respective  direction,  the output  effects  are 

discontinued (to save the life of the switching element) and the "sign" = "changes with " * "  
„ 

” – While the room temperature displayed differs from the set point by more than -2÷ +1°C, 

the controller switches for 4 minutes in forced “opening” or “closing” mode to reach the set room 
temperature more quickly. Visualized by blinking the "°c" sign alternatively with "R 
 
When "STOP" mode is enabled, row 2 alternately outputs "-STOP--"  
 
 

---------- PROXEL ENGINEERING ---------------- www.proxel-bg.com-------------------------------- 3WMREG rev. 2.4 /02.2017------      
 

 

          

 

 

Set T.   
[ 45ºC] 2

 

±Hist I  
[ 2ºC] 3

 

dTAlarm 
[ 65ºC] 5

 

±Hist II  
[ 10ºC] 4

 

ROOM T.25  
[ 45ºC] 1

 

Manual activation of outputs:

 

Press and hold 

„SET” 

button. 

Press  

„Up- ↑” 

button

 

to manual activation in the "open" mode 

Press the "Dn- ↓" button to manually activate in the "close" mode  
 
Using the Buttons for Parameters Adjustment:  
Navigates among screens: buttons 

„Up- ↑”

 and 

„Dn-↓”

To change required parameter – push the 

„Set

” button.  

Adjust the value using the buttons 

„Up- ↑”

 and 

„Dn-↓” .  

Confirm with the button

 „Set

 

 

*Note: Adjustment of all parameters is possible only after pressing the "Set" button indicated by 
placing the value in "[" and "]". Confirm the value again with the "Set" button.  

 
Window/Screen #1  - Room temperature

 

 

Display - set and readed room temperature. 

 

Row  1

:  Displays  the  selected  parameter  "ROOM  T."  and  the  room  temperature 

measured at 25°C  

     Row 2

: The value of the parameter. Range 10ºC ÷ 45ºC. 

Screen [1]

 

 

 
Window/Screen #2 - temperature set point

 

 

Display - set the operating temperature

 

Row 1

: Displays the selected parameter "Set T."

 

Row 2

: The value of the parameter. Range -10ºC ÷ 90ºC. 

Screen [2]

 

*  If  operation  mode is  based  on ambient temperature  this  value  is  automatically 

selected and can not be adjusted manually

 

 

 

Window/Screen #3 – Hysteresis fine adjustment 

Row 1

: Displays the selected parameter "± Hist I",  

Row 2

: The value of the parameter. Range 2ºC ÷ 10ºC. ". 

Screen [3] 

 

If there is a difference between the set point and reading below the selected value, 

the adjustment is made only by an integral factor.  
At a difference above the set value - adjustment is done with a fine step.  

* to change this parameter a password is required

 

 
Window/Screen #4 – Hysteresis of coarse adjustment

 

 

Row 1

: Displays the selected parameter “±Hist II 

 

Row 2

: The value of the parameter. Range “±Hist I” + 2ºC ÷ 15ºC. ”

Screen [4]

 . 

If the difference between the set and the achieved between Hist I and Hist II 

regulation is done fine.  
If the difference is outside the range, the adjustment is done with a coarse (fast) step.

 

 

* to change this parameter a password is required

 

 

 

Window/Screen #5 –Emergency closing / opening temperature

 

 

Row 1

: Displays the selected parameter “dTAlarm”.  

Row 2

: The value of the parameter. Range “Set.T”±35ºC.

Screen [5] .

   

 

* to change this parameter a password is required

 

 

-at "dTAlarm"> "Set T." to an emergency closing is reached if the measured value exceeds the "dT 
alarm” 
-in "dTAlarm" <"Set T." until emergency closing is reached when the measured value  reduces 
below "dT Alarm"

  

 