7.2 General Settings
– Communication
This section describes the configuration settings for remote communication; IP addresses, and general
settings for IEC 60870-5-101 and IEC 60870-5-104.
7.2.1 Communication
– Ethernet
The settings for
Ethernet
are found on the
Config/Communication/Ethernet
tab
:
Settings -
Ethernet
:
Parameter
Description
Range
Factory value
Unit
Settings for unit:
Enable static IP
Fixed or dynamic IP address (via DHCP).
Yes or No
Yes
-
IP address
Fixed IP address for the device.
1
192.168.0.31
-
Netmask
Netmask
1
255.255.255.0
-
Gateway
IP address for network gateway
1
192.168.0.1
-
Trusted IP addresses for IEC 60870-5-104:
IP address n
Address
n
of IEC 60870-5-104 master (
n
= 1, 2, … )
1
192.168.0.10n
-
Enable n
Accept connection from this address.
If no address is specified, connection is accepted
from all addresses (within the Netmask).
Yes or No
No
-
7.2.2 Communication
– IEC 60870-5-101/104
There are three sub-tabs on the
IEC 60870-5-101/104
tab, or four if the option
”
-
101 Master”
is enabled.
Each tab and its settings are described in the following chapter.
1
Range according to common notation (4 bytes in decimal form, 0..255). Observe that the address 0.0.0.0 is not
allowed.