2. BOILER CHARACTERISTIC AND EQUIPMENT

2.1. CHARACTERISTICS

PROTHERM electric boilers are designed for usage in heating warm-water systems with forced water circulation.

They serve as heaters of heating water, which is then pumped and distributed through central and level heating
systems to heating bodies.

The electric boiler has a function of sequential on/off switching of power at intervals of maximum 6 kW with 10-70

seconds delay according to the boiler output, so that undesirable impulses in the mains are eliminated on the
electric boiler switch-off and switch-on. The circulation pump only works when it is necessary, thereby saving
energy and reducing mechanical wear. The pump stays in operation for 2 minutes after the electric boiler switch-off,
so that warm water remaining in the boiler body and distribution system after switch-off can be utilized.

The electric boiler is mounted into a steel case with a front panel integrated with side panels attached to the back

panel with screws. The heating water inlet and outlet are at the bottom of the boiler as well as an electrical connection.

The REJNOK series boilers are designed for mounting on a wall.
In order to achieve higher output, the electric boilers can be cascade-connected, and controlled by only one

temperature controller connected to the primary electric boiler.

Operating diagram of the electric boiler (Diagram 1)

1. a heating coil
2. a container / heat exchanger
3. insulation
4. a deaerating valve
5. the circulation pump
6. heating flow
7. heating return
8. an integrated hydroblock
9. a safety valve
10.

a pressure sensor

11.

an expansion tank

2.2. Boiler equipment

The electric boiler is equipped with a cylindrical heat

exchanger with heating elements, a hydroblock consisting of
an integrated circulation pump, a pressure sensor and a safety
valve.

The signalling and power control panel consists of an

integrated thermometer and a pressure meter, an operating
thermostat, the first, second and third output level LED diodes,
the second and third output level switches, general remote
control LED diode and LED diode indicating mains and
eventual overheating of the boiler.

The internal control and safety segment consists of an

electronic switching block with a contactor for general remote
signal control and an emergency thermostat.

There is a built-in 10l expansion tank for the compensation

of the thermal expansivity effect of heating water in the system.

TS

1

2

3

4

5

6

7

8

9

10

11

Diagram 1

Содержание RAY 9-24K

Страница 1: ...Supplied By www heating spares co Tel 0161 620 6677 14 User and installation instructions for direct heating electric boiler RAY 9 24K y...

Страница 2: ...4 4 Conditions for installation and operation 5 5 Boiler connection dimensions and pump characteristics 6 6 Mounting and placement of the boiler 7 6 1 Wiring 7 6 2 Cascade control 8 7 Operations 8 8 M...

Страница 3: ...ed in the operating instructions and carry out everything in accordance with them 8 Do not remove or damage any labels or written notices on the boiler 9 The boiler complies with the following standar...

Страница 4: ...he REJNOK series boilers are designed for mounting on a wall In order to achieve higher output the electric boilers can be cascade connected and controlled by only one temperature controller connected...

Страница 5: ...um heating water temperature depends on the type of heating system floor heating fitting of thermostatic heads heating of hot water Please set the indoor temperature controller according to the user i...

Страница 6: ...boiler and a proof check are demonstrated on a Diagram 3 Provision of warranty is conditioned by professional installation carried out by an authorized service company Therefore please contact our co...

Страница 7: ...connection dimensions and pump characteristics Boiler connection description 1 a cable bushings 2 filling draining 1 2 3 a heating water inlet 3 4 4 overflow of a safety valve 5 a heating water outlet...

Страница 8: ...r distribution system several times with pressure water Older already used systems should be flushed in the direction which is opposite to the direction of the heating water In new systems all heating...

Страница 9: ...ditional sealing is made if necessary After completing installation the operating thermostat function is checked along with the thermal cut off pressure switch and control elements on the panel Note B...

Страница 10: ...the expansion tank and refill the lost water 9 Complete supply of parts The electric boiler is supplied in an assembled state The connecting wires for the electric boiler and connecting wires for the...

Страница 11: ...4 Filling draining opening G 1 2 Dimensions height mm 745 width mm 410 depth mm 240 weight without water kg 34 Efficiency 99 5 Max operating temperature of the heating water C 85 Max delivery of the...

Страница 12: ...620 6677 11 13 Boiler wiring diagram TS pressure switch 0 8 Bar HT over heat thermostat 100 C PT operating thermostat max 85 C PR1 PR2 room thermostat 230 V 0 1 A HDO ripple control S HDO RC contactor...

Страница 13: ...Z For a correct communication between the boiler and the DHW tank it necessary to fill following conditions which relate to a pic on the page No 13 Assembly conditions to a distribution a heating wate...

Страница 14: ...ontrol voltage 230 AC at the interconnection the electric boiler with the DHW tank it always necessary made it in accordance with conditions in user and installation instructions TS pressure switch 0...

Отзывы: