ENGLISH | AS-4080
15
B.2 Minimum opening of the window
This is determined by:
a.
The throughput of the air extraction device in m
3
/h
b.
The size of the window to be opened in m
2
.
c.
The size of the gap at the window in cm (see Table 1)
Most kitchens are equipped with rectangular combination tilt
& turn windows.
If the window is, for example, round in form, then ask your
specialist installation technician or the district flue & chimney
inspector to calculate the minimum opening.
An example of the required minimum opening for a rectangu-
lar window is shown in the table for tilt/turn adjustment.
B.3 Spreadsheet for determining the minimum
gap opening of your window
1. Find out the air extraction throughput of your air
extraction device in m
3
/h. You can find this on the type
B. Assembly instructions
We recommend that installation is performed by a profes-
sional. Proper installation guarantees safe and long-term
operation. The device must undergo a functional test by a
qualified technician or in German-speaking countries by the
Bezirksschornsteinfegermeister (district chimney and flue
inspector).
Caution!
Do not plug the AS-4080 into the power socket until the
magnetic sensor is mounted on the window.
B.1 Magnetic sensor (see Fig. 1)
Note
: With this model you must decide whether the window
has to be turned or tilted to actuate the air extraction hood.
A corresponding notice should be affixed to the window.
For correct location of the magnetic sensor, see Graphic 2.