ProTeam PC-NVI-110 Скачать руководство пользователя страница 16

14 

 

 

 

 

2. High-pressure switch 
is damaged

 

3.Refrigerant system 
block

 

4. EEV deadlock 

 

2.

  Check  if  high-pressure 

switch is off

 

3.

 Check if refrigerant system 

is blocked 

4.

  Switch  heat  pump  off, 

then  turn  it  on  and  off  to 
check  if  EEV  r e s e t   can 
be  heard. 

2.

  Replace high-pressure 

switch 

3.

  Replace filter  

 
4.Replace EEV 

 

 

P03 

 

Low pressure 
protection 

1. Lack of gas 
2.Refrigerant system 
block

 

3.Heat pump operating 
range exceeded 

1.

 Check  if  gas  system  is 

leaking 

2.

  Check if filter is blocked 

3.

  Check if ambient temp. or 

water temp.are above limits 

1.

 Repair the 

leak

  and refill with gas 

2.

 Replace filter 

 
 
 

P04 

 
 

T3 Coil 
overheat 
protection 

1.

  Heat  Pump 

fan 

discharge  area  is 
blocked 

2.

  Evaporator

 is blocked 

3.

  T3 

coil 

sensor 

position
 was      changed 

 

1.

 check if the discharge area 

is open/free 

2.

  check if the evaporator is 

blocked 

3.

 check if the coil sensor 

resistance value is correct 

 
 

1.

 Free up the discharge area 

2.

  Clean the evaporator 

3.

  Replace sensor 

 

P05 

Exhaust gas 
temperature 
protection 

1.

  Lack of gas 

2.

  sensor position 

was changed 

1.

 Check if there is a leak in 

the refrigerant system 

2.

 Check if the sensor 

resistance value is correct 

1.

 Repair leak and refill gas 

2.

 Replace sensor 

 
 
 
 

 

P06 

 
 
 

 

Outlet  water 
temperature 
anti-freezing 
protection 

 
 

1.

  lower water flow

 

2.

  heat exchanger 

blocked

 

3.

  Y-shaped filter 

blocked

 

4.

  Overlow load

 

 

1.

  check if there is air in 

water system

 

2.

 Plate heat exchanger if 

blocked

 

3.

  check if Y-shaped filter has 

block

 

4.

  check that design of 

indoor water system is 
appropriate, if there is a 
water bypass

 

1.

  If there is a problem 

with the drain valve, 
replace it

 

 

2.

  blow plate heat exchanger 

with water or high-pressure 
gas from the opposite 
direction

 

3.

  clean Y-shaped filter; 

4.

  water system must have 

bypass 

 
 

 

P07 

 

Pipe 
temperature 
anti-freeze 
protection 

 

1.

  lack of gas in system 

2.

  water sytem is 

blocked

 

3.

  cooling system is 

blocked

 

1.

  check system for 

leaks

 

2.

  check if Y-shaped filter 

is blocked

 

3.

  check if cooling system 

filter is blocked

 

 

1.

 Repair leak and refill gas

 

2.

 Clean Y-shaped filter

 

3.

 Change filter

 

 

P08 

 

High-pressure 
2 protection 

 

High pressure switch 2 
fault 

 

check if high pressure switch 
2 cuts out under unit  OFF 
condition 

 

change high pressure switch 2 

 

 

E01 

 

Controller 
communicatio 
n failure 

 

 

Communication 
cable fault 

 

Check communication cable  

 

Re-connect or change 
connection cable  

 

 

E02 

TP1 exhaust 
gas 
temperature 
sensor failure 

sensor temperature 
deviation or 
failure 

 

Check sensor 
resistance value or if 
sensor is faulty 

 

 

Re-connect cable or 
change sensor 

Содержание PC-NVI-110

Страница 1: ...Models PC NVI 90 PC NVI 110 PC NVI 140 PC NVI 170 PC NVI 210 PC NVI 230 PC NVI 270 PC NVI 320 Installation and Operation Manual PROTEAM EUROPA Swimming Pool Heat Pump ...

Страница 2: ... pool and extending your swimming season The Proteam Inverter Heat Pump is a smart heat pump which knows how to heat your pool and maintain its temperature in the most efficient way thanks to the full inverter technology Please read the manual carefully to get the maximum benefitfromyourheatpump Please read carefully ...

Страница 3: ...2 PARAMETER CHECKING AND ADUSTMENT 12 Parameter list 13 Malfunctioning of the unit and maintenance 13 MAINTAINING THE UNIT 16 Cleaning the pipe system in the heat exchanger 17 Cleaning the air system 17 Winter Shutdown Lay up 17 TROUBLESHOOTING 17 ENVIRONMENTAL INFORMATION 18 DISPOSAL REQUIREMENTS 18 WIRING DIAGRAM 19 Specification 21 READ THIS MANUAL CAREFULLY BEFORE STARTING UP THE UNIT DO NOT T...

Страница 4: ...functions are available Auto operation Auto restart Auto defrost Timer on off no human input required Wide temperature operating range 10 C to 46 C Reliable operation To ensure maximum performance and reliability of the unit multiple protection devices have been built into the units including insufficient water flow protection high low pressure protection overload protection compressor protection ...

Страница 5: ...capacityofthepowercircuitisinsufficientorthereisanincompleteelectricalcircuit itcouldresultin fire or electric shock Theunitmustalwayshaveanearthedconnection If the power supply is not earthed you must not connect the unit Neveruseanextensioncabletoconnecttheunittotheelectricpowersupply Ifthereisnosuitable earthedwallsocketavailable haveoneinstalledbyarecognizedelectrician Do not move repair the u...

Страница 6: ...ngers or other objects into the fan or evaporator Thefanrunsathighspeed itcouldcause serious injury ITEMS INSIDE PRODUCT BOX Beforestartingtheinstallation pleasemakesurethatallpartsarefoundinsidethebox The UnitBox Item Image Quantity Proteam Inverter Swimming pool heat pump 1 Installation and Operation Manual 1 Water Connectors 50mm 2 Winter Cover 1 Anti vibration rubber feet 4 Water Drainage Pipe...

Страница 7: ...5 OVERVIEW OF THE UNIT Unit Dimensions Model PC NVI 90 110 140 PC NVI 170 210 230 PC NVI 270 320 A 986 1076 1176 B 668 720 822 C 356 426 451 D 405 456 481 E 608 628 723 F 116 116 116 G 380 330 500 ...

Страница 8: ... control components 17 Low pressure switch 5 Finheatexchanger 18 Power waterproof cover 6 Fan blade 19 Controller 7 Middle panel 20 Rightpanel 8 AC fanmotor 21 Needle valve 9 Fan 22 Four wayvalve 10 FrontPanel 23 High pressurevalve 11 Discharge grill 24 Electronic expansion valve 12 Reactance waterproof box 25 Titaniumtubeheatexchanger 13 Reactance 26 Balance tank ...

Страница 9: ...oidpositioningheatpumponasurfacethatcantransmitvibrationstothe house Try to avoid placing appliance under a tree or exposed to water or mud which would probably make maintenance more difficult Waterconnection Theheat pumpisconnectedtoafiltrationcircuit withaby pass It isimperativethattheby pass is placedafterthepumpandthefilter The by passgenerallyconsistsof3valves This makes it possible to regula...

Страница 10: ...s purpose the heat pump must be raised by at least 10 cm Howtoinstallthecondensatedrainkit 1 Install your heat pump by raising it by at least 10 cm using solid moisture resistant studs 2 Connect the exhaust hose to the drain hole located underneath the heat pump Hydraulic Connection ...

Страница 11: ...gth of your cable is more than 10 meters we advise you to seek advice from a professional A voltage variation of 10 during operation is acceptable The power supply lines must be securely fastened The cable must be suitable for outdoor use The filter must be cleaned regularly to ensure that the water in the system is clean and to avoid any problems related to dirt or clogging of the filter Heat pum...

Страница 12: ...wntooperatingthedigitalcontroller NEVER LET THE DIGITAL CONTROLLER GET WET THIS MAY CAUSE AN ELECTRIC SHOCK OR FIRE NEVER PRESS THE BUTTONS OF THE DIGITAL CONTROLLER WITH A HARD POINTED OBJECT THISMAYDAMAGETHEDIGITALCONTROLLER NEVERINSPECTORSERVICETHEDIGITALCONTROLLERYOURSELF ASKAQUALIFIED SERVICE PERSON TO DO THIS 1 Controller Instruction 1 1 General Input Voltage DC12V RS485 Communication Short ...

Страница 13: ...mode Long Press to enter menu option Increase Temperatureset orpreviousscreen Decrease Temperature set or next screen Boost Runningmode Short presstoenter Smart Runningmode Short presstoenter Silent Runningmode Short presstoenter 2 2 Intructions for Display Symbols Heatingmode Cooling mode Auto runmode Boost mode Smartmode Silentmode wifi function when applicable HeatPumpoutputcapacityinrealtime W...

Страница 14: ...30 seconds the controller will save the last setting and go back to original surface 3 3Set Parameter When heat pump is on Long press into memu displays Parameter Query press or select among Parameter Query Parameter Setting Debugging Status History Fault Short press to confirm your selction and switch to press or select displays the value When on status of Parameter Setting and display two 88 it ...

Страница 15: ...17 Voltage Current 10 18 Standby 19 Standby 20 Standby 21 Fan speed Current 10 Malfunctioning of the unit and maintenance When anerror occurs or the protection mode is set automatically the circuit board and the wired controllerwillbothdisplaytheerrormessage Error Meaning Analysis Diagnosis Solution P01 Water Flow failure 1 No water flow 2 Flow switchfailure 3 Water systemblock 1 Check if water in...

Страница 16: ...orrect 1 Repair leak and refill gas 2 Replace sensor P06 Outlet water temperature anti freezing protection 1 lower waterflow 2 heat exchanger blocked 3 Y shaped filter blocked 4 Overlow load 1 checkifthere is airin water system 2 Plateheatexchangerif blocked 3 checkifY shapedfilterhas block 4 check that design of indoor water system is appropriate if there is a water bypass 1 If there is a problem...

Страница 17: ... Check sensor resistance valueorif sensoris faulty Re connect cable or change sensor E08 T6inletwater temperature sensor failure sensor temperature deviation or failure Check sensor resistance valueorif sensoris faulty Re connect cable or change sensor E09 T7outletwater temperature sensor failure sensor temperature deviation or failure Check sensor resistance valueorif sensoris faulty Re connect c...

Страница 18: ...adjustment data E33 IPM adjustment data E34 AC input voltage abnormal E35 IPM adjustment data E36 Reserved E37 IPMmodule current frequency limits E38 IPMmodule voltage frequency limits E51 Failure of fan motor drive UNIT MAINTENANCE To protect the paintwork avoid leaning orputtingobjects on the unit The outer casing of the heat pump parts can be wiped with a damp cloth and domestic cleaner Warning...

Страница 19: ...appens the ice must be removed in the vicinity of the air intake and exhaust air outlet grids toensure thattheminimumairflowrate ismaintained Winter Shutdown If there is a chance of freezing after the bathing season has ended when the swimming pool heating is switchedoffandtheexternaltemperatureisexpectedtodropbelowtheoperatinglimit thewatercircuit of theheat pump shouldbe completelydrained Otherw...

Страница 20: ...ins R410A refrigerant inthe amount as stated in the specification Do not discharge R410A into the atmosphere R410A is a fluorinated greenhouse gas with a Global WarmingPotential GWP 1975 DISPOSALREQUIREMENTS Dismantlingoftheunit treatmentoftherefrigerant ofoilandofotherpartsmustbedoneinaccordance withrelevantlocalandnationallegislation Yourproductismarkedwiththissymbol Thismeansthatelectricalandel...

Страница 21: ...19 Model PC NVI 90 110 140 170 210 230 SW1 1 SW1 2 Model OFF OFF OFF ON ON OFF ON ON ...

Страница 22: ...20 Model PC NVI 270 320 ...

Страница 23: ... 76 5 71 capacity kW Silent 2 98 4 07 5 33 6 50 COP Silent 6 67 6 53 6 53 6 47 Air35 Water28 Humidity 80 capacity kW 1 8 4 6 2 4 6 0 3 2 7 87 3 9 9 6 power input kW 0 28 1 2 0 33 1 39 0 43 1 78 0 51 2 3 EER 4 47 7 46 4 32 7 34 4 41 7 42 4 24 7 4 capacity kW Boost 4 60 6 00 7 87 9 60 EER Boost 4 47 4 32 4 41 4 24 capacity kW Smart 3 68 4 80 6 30 7 68 EER Smart 5 59 5 40 5 51 5 30 capacity kW Silent...

Страница 24: ...apacity kW Silent 7 85 8 67 10 14 11 84 COP Silent 6 80 6 40 6 60 6 53 Air35 Water28 Humidity 80 capacity kW 4 3 11 5 5 3 12 8 6 2 15 7 2 17 5 power input kW 0 57 2 62 0 73 3 1 0 82 3 48 0 97 4 17 EER 4 38 7 48 4 17 7 25 4 29 7 54 4 21 7 44 capacity kW Boost 11 5 12 80 15 00 17 50 EER Boost 4 38 4 17 4 29 4 21 capacity kW Smart 9 20 10 24 12 00 14 00 EER Smart 5 48 5 21 5 36 5 26 capacity kW Silen...

Страница 25: ...f the refrigerant of oil and ofother partsmust be done in accordancewithrelevantlocalandnationallegislation Yourproductismarkedwiththissymbol Thismeansthatelectricalandelectronic productsshallnotbemixedwithunsortedhouseholdwaste Do not try to dismantle the system yourself the dismantling of the system treatment of the refrigerant ofoilandotherpartsmustbedonebyaqualifiedinstallerinaccordancewithrel...

Отзывы: