Setup
Page 52 of 87
In the Module Properties dialog, enter the IP address, the assembly instance, and size for the
input, output, and configuration. Below are the required connection parameters.
Connection Parameter
Assembly Instance
Size
Input
100
34 (32-bit)
Output
101
1 (32-bit)
Configuration
102
0 (8-bit)
Table 3.4 - RSLogix class 1 connection parameters for the PLX51-DF1-ENI
Figure 3.54 - RSLogix General module properties in RSLogix 5000
NOTE: You will need to enter the exact connection parameters before the
module will establish a class 1 connection with the Logix controller.
Next, add the connection requested packet interval (RPI). This is the rate at which the input
and output assemblies are exchanged. The recommended value is 500ms. Refer to the
technical specification section in this document for further details on the limits of the RPI.
NOTE: Although the module is capable of running with an RPI of 10ms, it is
recommended to set the RPI to 500ms to avoid unnecessary loading of the
module processor.
Содержание PLX51-DF1-ENI
Страница 1: ...PLX51 DF1 ENI DF1 Router DF1 to EtherNet IPTM Router June 27 2019 USER MANUAL ...
Страница 2: ...Preface Page 2 of 87 ...
Страница 9: ...Preface Page 9 of 87 Figure 1 4 Remote MicroLogix System Figure 1 5 Remote Programming Half duplex ...
Страница 62: ...Operation Page 62 of 87 ...
Страница 69: ...Diagnostics Page 69 of 87 Figure 5 6 Map Item status ...
Страница 78: ...Page 78 of 87 ...
Страница 82: ...Appendix Page 82 of 87 7 Here are example values after a successful MSG In the MicroLogix 1100 In the L36ERM ...
Страница 86: ...Page 86 of 87 ...