![ProSoft Technology PLX51-DF1-ENI Скачать руководство пользователя страница 24](http://html.mh-extra.com/html/prosoft-technology/plx51-df1-eni/plx51-df1-eni_user-manual_1618990024.webp)
Setup
Page 24 of 87
The Serial - DF1 configuration tab is shown in the figure below. The DF1 Serial configuration
window is opened by either double clicking on the module in the tree or right-clicking the
module and selecting Configuration.
Figure 3.15 - Serial DF1 configuration
The Serial – DF1 configuration tab consists of the following parameters:
Parameter
Description
Protocol
The protocol parameter configures the module to operate in full duplex, half
duplex, or Radio Modem mode on the DF1 network.
BAUD Rate
The BAUD rate configures at what speed the data is sent across the RS232 serial
network. The module provides the following speeds:
1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200
Parity
This parameter configures the parity of the module’s RS232 serial port. The
module allows for Even, Odd, or None parity setting.
Error Detection
The module can be configured to perform either BCC or CRC checksum validation
on incoming and outgoing packets. CRC checksums is a much stronger validation
method when compared to BCC but is more processor intensive to perform.
Embedded Responses
This parameter configures the module to add the acknowledge responses in the
data payload. You can configure the module to be Auto Detect or On.
This function is only available in Full Duplex mode.
Bridge Half-Duplex Mode
This parameter configures the port as a DF1 Slave or DF1 Master.
Содержание PLX51-DF1-ENI
Страница 1: ...PLX51 DF1 ENI DF1 Router DF1 to EtherNet IPTM Router June 27 2019 USER MANUAL ...
Страница 2: ...Preface Page 2 of 87 ...
Страница 9: ...Preface Page 9 of 87 Figure 1 4 Remote MicroLogix System Figure 1 5 Remote Programming Half duplex ...
Страница 62: ...Operation Page 62 of 87 ...
Страница 69: ...Diagnostics Page 69 of 87 Figure 5 6 Map Item status ...
Страница 78: ...Page 78 of 87 ...
Страница 82: ...Appendix Page 82 of 87 7 Here are example values after a successful MSG In the MicroLogix 1100 In the L36ERM ...
Страница 86: ...Page 86 of 87 ...