Battery Life Advisory
The modules use a rechargeable Lithium Vanadium Pentoxide battery to back up the real-time clock and
CMOS. The battery should last for the life of the module. The module must be powered for approximately
twenty hours before the battery becomes fully charged. After it is fully charged, the battery provides backup
power for the CMOS setup and the real-time clock for approximately 21 days. When the battery is fully
discharged, the module will revert to the default BIOS and clock settings. The battery is not user
replaceable.
Electrical Ratings
ControlLogix®
Backplane Current Load: 800 mA @ 5.1 Vdc; 3 mA @ 24 Vdc
Operating Temperature: 0°C to 60°C (32°F to 140°F)
Storage Temperature: -40°C to 85°C (-40°F to 185°F)
Shock: 30 g, operational; 50 g, non-operational; Vibration: 5 g from 10 Hz to 150 Hz
Relative Humidity: 5% to 95% with no condensation
All phase conductor sizes must be at least 1.3 mm
2
and all earth ground conductors must be at least
4mm
2
.
CompactLogix™
Backplane Current Load: 500 mA @ 5.1 Vdc; 3 mA @ 24 Vdc
Operating Temperature: 0°C to 60°C (32°F to 140°F)
Storage Temperature: -40°C to 85°C (-40°F to 185°F)
Shock: 30 g, operational; 50 g, non-operational; Vibration: 5 g from 10 Hz to 150 Hz
Relative Humidity: 5% to 95% with no condensation
All phase conductor sizes must be at least 1.3 mm
2
and all earth ground conductors must be at least
4mm
2
.
Agency Approvals and Certifications