PC56
♦
ControlLogix Platform
Installing the PC56 Embedded PC
In-Rack Industrial PC
Quick Start Guide
Page 12 of 25
ProSoft Technology, Inc.
November 18, 2009
If you are inserting multiple modules, make sure that all of the modules are
aligned with their respective slots before you snap them into place.
1.5 Connecting
Peripherals
Just like any other PC, the PC56 is fully equipped for connections to a variety of
devices. The inside label provides descriptions of the various ports and
connectors.
Caution:
Make sure power to the ControlLogix rack is OFF before connecting peripherals to the
PC56.
1.5.1 Cable
Connections
The application ports on the PC56 module support RS-232, RS-422, and RS-485
interfaces. Please inspect the module to ensure that the jumpers are set correctly
to correspond with the type of interface you are using.
Note:
When using RS-232 with radio modem applications, some radios or modems require
hardware handshaking (control and monitoring of modem signal lines). Enable this in the
configuration of the module by setting the UseCTS parameter to 1.