Configuration Webpage
ICX30-HWC ♦ Industrial Cellular Gateway
User Manual
3G Cellular (M2M)
Page 30 of 64
ProSoft Technology, Inc.
June 22, 2015
Modbus Point-To-Multipoint
Description
Server/Client
Server = ICX30-HWC serial port is connected
to one or more Modbus slaves
Client = ICX30-HWC serial port is connected
to a Modbus master
TCP/IP Protocol
UDP
Remote ICX30 Server IP
Address
(Server mode only) WAN IP address of
Modbus master radio
Port
Modbus service port, usually 502
Listen Port No.
(Client mode only) Defines the Modbus
service port to listen to
Modbus
RTU or ASCII
Add Address
Mapping
(Client mode only) WAN IP address of
Modbus slave radio
Start ID
(Client mode only) Slave ID start
End ID
(Client mode only) Slave ID end
DF1
Description
ICX30 Serial Port
Master/Slave
Master = ICX30-HWC serial port is connected
to a DF1 master
Slave = ICX30-HWC serial port is connected
to one or more DF1 slaves
Listen Port Number
(Master mode only) Defines which DF1
service port to listen to
Add Remote ICX30
Address
(Master mode only) IP address of a remote
ICX30 connected to a DF1 slave
Slave ID
(Master mode only) DF1 slave ID of remote
DF1 slave
Remote ICX30 Master IP
Address
(Slave mode only) IP address of remote
ICX30 connected to a DF1 master
Port
(Slave mode only) Service port of remote
ICX30 connected to a DF1 master