Models: 

DPM2-P-HL 

DPM2-P-2R-HL

u

Ser

 M

anual

Scan or click the QR code for a series of Configuration and Programming 

videos for the ProSense DMP Series Panel Meters

Содержание DPM2-P Series

Страница 1: ...Digital Panel Meter Frequency Rate Tachometer Counter Modes Models DPM2 P HL DPM2 P 2R HL User Manual Scan or click the QR code for a series of Configuration and Programming videos for the ProSense D...

Страница 2: ...Wiring Examples 9 Wiring for Magnetic Sensor and Switched Contact Input Signal 9 Wiring for NAMUR Sensor Input Signal 9 Wiring for NPN PNP and TTL 24V DC Encoder 9 AC Voltage Input Signal Wiring 9 Rel...

Страница 3: ...y 19 1 2 3 and 4 control modes for counter mode Cont and Setpoint 2 only 20 Pulse output PuLS Counter mode only Cont 21 Latched output LAtC Counter mode only Cont 21 RESET TOTALIZER and MAX MIN Functi...

Страница 4: ...ding waste of electrical and electronic equipment from products put on the market after August 13 2005 the user can give it back without any cost to the place where it was acquired to proceed to its c...

Страница 5: ...ions Description The ProSense DPM2 P series offers a simple low cost digital display for counter tachometer rate and frequency applications The DPM2 P has a 4 digit 14mm character height red LED displ...

Страница 6: ...TTL 24V encoder Switched contact AC or DC powered Optional 2 Form C SPDT relays N O or N C operation Activation on increasing or decreasing input signal Hysteresis or time delay operation tach and rat...

Страница 7: ...m the panel pull the rear fixing clips latching tabs outwards until they are disengaged then slide the fixing clips back over the case Wiring Terminals CN3 1 2 CN2 1 2 3 4 5 6 7 CN1 CN4 1 2 3 4 5 6 Ou...

Страница 8: ...als CN2 and power terminals CN1 2500Vrms for 1 minute to signal terminals CN2 and relays terminals CN3 or CN4 2500Vrms for 1 minute to power terminals CN1 and relays terminals CN3 or CN4 Refer to the...

Страница 9: ...ng for NAMUR Sensor Input Signal DPM2 P NAMUR SENSOR 3 2 EXC 8V DC IN EXC OUT Wiring for NPN PNP and TTL 24V DC Encoder DPM2 P SENSORS NPN PNP TTL 24V DC ENCODER 2 1 EXC 24V DC IN COMMON EXC OUT 4 IN...

Страница 10: ...ACT Note In both cases main counter RESET is activated through 1 and 5 terminals when contact is closed and it remains active until the contact is again opened Remote totalizer RESET is not available...

Страница 11: ...es when setpoint 1 turns active 5 UP key Main counter Reset when pressed 3s Shows setpoint value Increases value of active digit 6 SHIFT key Displays maximum and minimum stored values tachometer mode...

Страница 12: ...sible to see programmed information and that it is not allowed to modify any parameter from the entire configuration In this visualization mode the meter automatically switches back to RUN mode after...

Страница 13: ...is chosen and ENTER key is pressed by repeatedly pressing the SHIFT key the display will show the three available operating modes Counter Cont rpm meter tACH and rate meter rAtE In counter mode the m...

Страница 14: ...configurable factor and then 1 000 with first of the four digits flashing This factor can be programmed from 0 001 to 9 999 Display will increase according to the programmed multiplying factor This f...

Страница 15: ...ved at the input input frequency If increasing frequency must result in an increasing display then dir direct proportional variation must be selected Select inV reverse proportional variation if incre...

Страница 16: ...e and FrEC and diSP for rate mode should operate correctly However depending on the sensor type it may be necessary to modifiy internal measurement times After defining decimal point position at the e...

Страница 17: ...oes to zero The value for this parameter must always be greater or equal to possible minimum period of input signal Once tLiM value is entered press again ENTER to save changes Relay Setpoints Configu...

Страница 18: ...c Normally closed contact PULSE OR LATCHED OUTPUT PuLS Pulse output with activation time configurable from 0 1 to 99 9s LAtC Latched output Tachometer Mode tACH and rAtE ACTIVATING MODE Hi High level...

Страница 19: ...p to 99 9 seconds Time delay activation starts when display value reach each Setpoint SET either increasing or decreasing reaching the dly delay in output activation deactivation as right figure shows...

Страница 20: ...ective Setpoint value MODE 3 RESET Relay 1 activates at its Setpoint value When main counter reaches Setpoint 2 a main counter RESET is done Relay 2 output is pulse type and remains active for the pro...

Страница 21: ...available only when operating as a counter and it is not possible to disable it It consists in a 6 digit counter that increases at every received pulse applying the configured factor Totalizer value...

Страница 22: ...lowed by the minimum value and finally a third press shows run to go back again into RUN mode MAX MIN RESET function activates when visualizing maximum or minimum values SHIFT key is pressed for at le...

Страница 23: ...red through SHIFT and UP keys Finally press ENTER to validate and return to RUN mode Access to lock out configuration menu To access this menu from RUN mode press ENTER key for at least 3 seconds Disp...

Страница 24: ...arameters Under these conditions when entering main menu initial indication will be dAtA instead of Pro When no option is selected the next step to configure a partial lock out is displayed When a par...

Страница 25: ...meter tACH or rAtE When lock out is enabled selecting yES it is not possible to visualize maximum or minimum values by pressing SHIFT key although meter internally continues detecting and saving new e...

Страница 26: ...Sensor RC 1k ION 1mA DC IOFF 3mA DC NPN PNP Sensors Input RC 1k Logic level 0 2 4 VDC Logic level 1 2 6 VDC TTL 24V Encoder Input Logic level 0 2 4 VDC Logic level 1 2 6 VDC Switched Contact Input VC...

Страница 27: ...unter and totalizer Keypad Remote RESET counter Switched contact MAX MIN and MAX MIN RESET functions tachometer rpm or rate modes Keypad Relay 2R option Maximum switching current resistive load 8A Max...

Страница 28: ...rumentation Configuration Notes INPUT TYPE MODE DISPLAY MULT FACTOR OFFSET PPR DISP VARIATION INPUT FREQUENCY DISPLAY TMAX TLIM SETPOINTS SET1 ACT MODE DLY PULSE TIME HYS LATCH SET2 CONTROL MODE ACT M...