TROUBLESHOOTING

Troubleshooting with Status Indicator Assistance

1. Pilot burner must be lit. If not, push and hold Pilot knob and light pilot with 

piezo. Error code will be displayed when thermopile heats up. Error code 

can be recognized by counting the number of flashes of the status indicator 

after a three second pause. One single flash indicates that the control is in 

normal operation.

2. Observe status indicator on control; check and repair the system as noted 

in Table 3 below. Flash codes are displayed with a three-second delay 

between cycles. A continuous solid light indicates system shutdown when 

knob is turned from a temperature setting to OFF position. When the solid 

light is present, the pilot and main valve will not hold. When the status 

indicator goes out, the user can restart the system. (Approximate shutdown 

time is one minute.)

3. After status indicator analysis and appliance repair is complete, turn 

device knob to OFF, wait until the indicator goes out, then perform 

lighting procedure.

4. Status indicator light should be in normal mode (1 flash) with the knob in the 

PILOT position. Turn the device knob past the water temperature at which 

the tank should turn on the main burner. The status indicator light should 

continue to blink once every three seconds when there is a call for heat.

5. In the event of multiple failure codes, the next failure code follows the 

previous failure code by approximately three seconds with higher flash 

count first.

Table 3. Troubleshooting with status light visual indication.

LED Error

Code**

Number of LED Flashes*

Detected Failure

Recommended Action

Normal operation. 

Knob in PILOT 

position.

1 flash every 

3 seconds

☐  ☐  ☐  ☐

Not an error; indicates the electronics are 

holding the Pilot Valve open and the Main 

Valve closed.

You can now turn the knob to a desired 

setpoint temperature. LED will continue to 

flash 1 time every 3 seconds while in Idle 

mode (no call for heat).

Normal operation. 

Knob in HEAT 

position.

1 flash every 

3 seconds

☐  ☐  ☐  ☐

Not an error; indicates call for heat during 

normal operation, main valve open.

None.

Action required.

2 flashes

☐☐  ☐☐  ☐☐  ☐☐

Low thermopile voltage; main valve not 

turned ON.

Check thermopile and its connections. 

Check pilot flame.

4 flashes

☐☐☐☐  ☐☐☐☐

Temperature cut-out limit reached.

Check the valves and the water 

temperature sensor. Reduce the water 

temperature setpoint. Thoroughly check 

out main valve operation and water 

temperature control before walking away.

5 flashes

☐☐☐☐☐

Water temperature sensor failure.

Check water temperature sensor and its 

connection for open circuits, shorts or 

differences in resistance between the two 

sensor elements.

6 flashes

☐☐☐☐☐☐

Tank leakage detected by 

accessory module.

Control recovers after receiving message 

from accessory module.

7 flashes

☐☐☐☐☐☐☐

Electronics failure

Replace control module.

8 flashes

☐☐☐☐☐☐☐☐

This is just a warning; the control does not 

see power decaying with the knob in the 

OFF position.

Check valves.

Solid ON

Not an error – indicates that the control is 

in OFF mode.

None; wait until LED turns off if you want 

to restart the system.

*LED Error Codes are flashed once per second, with a three-second pause between repeating the error code.
**Maximum two different errors can be displayed simultaneously if more than one error has been detected.

Содержание PSW12414

Страница 1: ...tact with the control Where chemicals are suspended in air as in some industrial or agricultural applications protect the control with a cover Dust or Grease Accumulation Heavy accumulations of dust o...

Страница 2: ...Fuel Gas Code ANSI Z223 1 NFPA No 54 whichever applies Tubing installation must comply with approved standards and practices 1 Use a new properly reamed pipe free from chips If tubing is used make su...

Страница 3: ...ocedure 1 Start by turning the device knob to PILOT push the knob down and hold in position The pilot valve opens and allows gas to flow into the pilot burner NOTE If the gas pipe is full of air new i...

Страница 4: ...iance nameplate 3 IF CHECKING GAS INPUT WITH MANOMETER Make sure the manual gas shutoff switch is in the OFF position before removing outlet pressure tap plug to connect the manometer pressure gauge M...

Страница 5: ...flash count first Table 3 Troubleshooting with status light visual indication LED Error Code Number of LED Flashes Detected Failure Recommended Action Normal operation Knob in PILOT position 1 flash e...

Страница 6: ...pile for maximum output Thermopile output with time Fig 7 Thermopile output Follow diagram in Fig 6 Fig 6 Troubleshooting without status light Troubleshooting guide without status light TURN DEVICE KN...

Страница 7: ...g instructions provided by the manufacturer of your water tank appliance The information in this form describes a typical water heater control application but the specific controls used and the proced...

Отзывы: