10.1.5 Parameters [Level]
Mode
Menu
Archive
Reset
Pressure sensor parameter
System stop
Level
Water
Powder
Liquid
Stirrer
Level Max Max:
Level Max:
Level Min:
Level Min Min:
A0829
Start Polymer:
Fig. 28: Parameters [Level]
Parameter
Remark
Level Max Max
The
[Level Max Max]
is used to monitor for overfilling. If overfilling occurs, an
[Overfill]
alarm is
signalled.
Level Max
If the
[Level Max]
is exceeded, Ultromat preparation is stopped.
Start Polymer
If the
[Start Polymer]
level is exceeded, polymer metering and the stirrer start.
Level Min
If the
[Level Min]
is undershot, Ultromat preparation is started
Level Min Min
If the
[Level Min Min]
is undershot, an alarm message appears and the release for extraction is
cancelled.
Switching level of the continuous flow system:
400
1000
2000
4000
Max-Max
900
1000
1350
1450
Max
850
930
1290
1360
Start Polymer
560
620
860
900
Min
300
320
380
480
Min-Min
140
150
180
200
All values given in millimetres
Operating Menu [F2]
50