10.1.5 Parameters [Level]
Mode
Menu
Archive
Reset
Pressure sensor parameter
System stop
Level
Water
Powder
Liquid
Stirrer
Level Max Max:
Level Max:
Level Min:
Level Min Min:
A0829
Start Polymer:
Fig. 27: Parameters [Level]
Parameter
Remark
Level Max Max
The
[Level Max Max]
is used to monitor for overfilling. If overfilling occurs, an
[Overfill]
alarm is
signalled.
Level Max
If the
[Level Max ]
is exceeded, Ultromat preparation is stopped
Level Min
If the
[Level Min]
is undershot, Ultromat preparation is started
Level Min Min
If the
[Level Min Min]
is undershot, an alarm message appears and the release for extraction is
cancelled.
Switching level of the continuous flow system:
ULFa
400
1000
2000
4000
6000
8000
Max-Max
370
710
860
1320
1320
1310
Max
300
565
710
1105
1105
1105
Min
190
310
390
490
490
490
Min-Min
120
190
190
190
190
190
All values given in millimetres
Operating Menu [F2]
51