Dulcodes UV-Desinfektionsanlage
Page 45
Pr
o
Minent
®
Settings
Lower/upper band:
This processing mode allows you to control a pump via an electrical signal as shown in the
diagrams below.
Lower band
Upper band
e.g. Alkali pump
e.g. acid pump
I [mA]
I 1
I 2
F2
F1
0
20
P1
P2
F
max
I [mA]
I 1
I 2
F1
0
20
P1
P2
F2
F
max
Fig. 22
Fig. 23
Lower band:
The symbol
appears in the LCD display. The S1Ca will operate below I1 at F1.
Above I2, the S1Ca ceases to operate. Between I1 and I2 the stroke rate is between F1 and F2,
propor-
tional to the signal current.
Upper band:
The signal
appears in the LCD display. The S1Ca will cease to operate below I1.
Above I2, the S1Ca will operate at F2. Between I1 and I2 the stroke rate between is F1 and F2,
proportional to the signal current.
The smallest processable difference between I1 and I2 is 4 mA.
Error processing
In the “ER” (error) menu option you can activate an error processing function for the “curve”
mode. An error message appears for signals below 3.8 mA and the S1Ca stops.
7.4.3
Settings for “contact” operating mode (CONTCT menu)
In addition to those settings menus described in 7.5, there is an additional CONTCT in the
overall SET menu for the “contact” operating mode.
The operating mode “contact” allows you to activate a single stroke or a series of strokes. The
strokes can be activated by a pulse or via the “external control” terminal. This operating mode
is intended to transfer input pulses into a reduction (fraction) or small increase in strokes.
NOTICE
The factor resets to “1” if you change to a different operating mode.
The following versions are available:
•
Contact - identity code: external 1:1
•
Contact - identity code: external with pulse control