6. Place hex wrench in the top #4 cam set screw, loosen and move 
cam back counterclockwise and then clockwise into the switch until the 
switch “clicks”. Then move 1 degree further into the switch and snug 
up on the set screw. This will assure the aux switch will “trip” before 
the actuator reaches it’s end of travel.

7. Apply  Power  to  the  actuator  and  generate  a  MAXIMUM  position 
control signal (as set with the DIP switch selection above). The actuator 
will drive to its full CCW position and stop. If the STOP position is not 
calibrated  properly  (valve/damper  not  fully  OPEN  or  CLOSED),  the 
stop cam will need to be adjusted as follows:

 

Remove  power  from  the  actuator.  Insert  a  2.5mm  hex  key 

into the #1 cam and loosen the setscrew. Rotate the cam clockwise 
to  make  the  actuator  drive  further  OPEN  (later),  or  rotate  the  cam 
counterclockwise to have the actuator stop sooner. Make only SMALL 
adjustments each move. Reapply power and check the new setting. 
Snug up on the set screw when adjustment is correct.

5. Apply  Power  to  the  actuator  and  generate  a  MINIMUM  position 
control  signal  (as  set  with  the  DIP  switch  selection  above).  The 
actuator will drive to its full CW position and stop. If the STOP position 
is not calibrated properly (valve/damper not fully OPEN or CLOSED), 
the stop cam will need to be adjusted as follows:

 

Remove power from the actuator. Insert a 2.5mm hex key into 

the #2 cam and loosen the setscrew. Rotate the cam counterclockwise 
to  make  the  actuator  drive  further  CLOSED  (later),  or  rotate  the 
cam clockwise to have the actuator stop sooner. Make only SMALL 
adjustments each move. Reapply power and check the new setting. 
Snug up on the set screw when adjustment is correct.

Calibration-

Page 3 of 6   P1.A..P Series 

4.  With  the  power  OFF,  set  the  8  position  DIP  switch  for  proper 
operation. 

For 4-20mA Input, 1 is ON, 2 is OFF (default)

For 1-5vdc Input, 1 is OFF, 2 is OFF
For 2-10vdc INput, 1 is OFF, 2 is ON

For 4-20mA Feedback, 3 is OFF, 4 is ON, 5 is OFF (default)

For 2-10vdc Feedback, 3 is ON, 4 is OFF, 5 is ON

For Direct Acting (5v/10v/20mA = OPEN) 6 is OFF (default)

For Reverse Arcing (5v/10v/20mA = CLOSED) 6 is ON

Loss of signal drives CLOSED, 7 is OFF, 8 is ON
Loss of signal drives OPEN, 7 is ON, 8 is OFF

Loss of signal Fails in position, 7 is ON, 8 is ON (default)

FM1

1

_

P1
A_
P

_

F078P17 V

er C 01051

1

LED’S ON BOARD:
Yellow = Power On
Green = Drive Open
Red = Drive Closed

Отзывы: