Promation Engineering P1 A P Series Скачать руководство пользователя страница 2

PROMATION
ENGINEERING

Precision Actuation for Industry

3.  Make  the  electrical  connections  as  shown  below.  Connect  HOT  and  NEUTRAL  to  terminals  5  &  4  respectively. 
Connect a pair of control wires to the control card terminals marked  6 (COM) and 7 (+IN). The positive wire MUST 
connect to terminal 7, otherwise the controller will not function. Optionally, a pair of wires may be connected to terminals 
11 (COM) and 12 (+OUT) for remote position indication. Terminals A-F are for the (adjustable) aux switches.

Do NOT apply power at this time.

Connections and Settings-

This actuator has been factory calibrated to operate between 0

0

 and 90

0

. Most quarter-turn products will not require 

recalibration of these settings. Actuator is shipped in the fully CW position. Driving OPEN will rotate the actuator 
CCW (as viewed from above). If no adjustments are necessary, proceed to page 5 “Application Notes”. Otherwise, 
proceed to step 5 for the recalibration procedure.

Page 2 of 6   P1.A..P Series 

2. Remove the four screws from the BOTTOM 
of  the  enclosure  casting  to  facilitate  the 
removal of the cover and spacer casting. This 
will  allow  easier  access  to  the  control  wiring 
and cam adjustments as needed. 

1. The actuator is shipped from the factory in 
its fully CLOSED position. This can be verifi ed 
by  viewing  the  indicator  on  the  TOP  of  the 
actuator. Red is CLOSED, Yellow is OPEN.

SW1 OPEN Stop

(Factory Set - Fixed)

SW2 CLOSE Stop

(Factory Set - Fixed)

AUX SW3

(Factory Set - Adj)

AUX SW4

(Factory Set - Adj)

Internal Cam layout

FM1

1

_

P1

A_

P

_

F078P17 V

er C 01051

1

E

F

C

A

B

6

5

4

2

1

GND Screw

HEATER

FIELD WIRING

 (BY OTHERS)

INTERNAL WIRING

 (FACTORY)

GND

12

11

7

SIGNAL IN +

SIGNAL IN -

FEEDBACK OUT +

FEEDBACK OUT -

DC DRIVE

MOTOR

ALL SWITCHES

SHOWN WITH

ACTUATOR IN

FULL OPEN

POSITION

M

SW3

SW4

AUXILIARY

SWITCH

(STANDARD)

AUXILIARY

SWITCH

(STANDARD)

CLOSED*

NOT CLOSED*

NOT OPEN*

AUX SW COM*

OPEN*

* CONNECTIONS

OPTIONAL

Close

POSITION

FEEDBACK

1K ohm

SW1

SW2

HOT or DC+

NEU or DC-

12/24/120/230VAC

12/24VDC

Travel

STOP

Switches

Отзывы: