Service setting manual
35
ENG
Para-
me-
ter
Parameter name
Parameter description
Setting
range
Default
setting
P3.1
HEAT CURVE STEEPNESS
Heating curve steepness indicates what temperature is required
for the heating bodies by a determined outdoor temperature.
See chapter Heating curve.
0,2 ÷ 2,6
0,7- floor
1,0-
radiators
P3.2
PARALLEL SHIFT OF HEATING
CURVE
Setting of parallel shift of heating curve or calculated stand-pipe
temperature.
Use this setting to eliminate deviation between actual and requi-
red room temperature.
-15 ÷ 15 °C
0
P3.3
DURATION OF BOOST HEATING Duration of boosted room temperature by changeover from night
to day heating period.
0 ÷ 200 min
0
P3.4
ROOM TEMPERATURE INCREA-
SE BY BOOST HEATING
Boost room temperature increase by changeover from night to
day heating period.
0 ÷ 8 °C
3
P3.5
HEAT CURVE STEEPNESS FOR
ADDITIONAL DIRECT CIRCUITS
Setting of heat curve steepness for additional direct heating
circuits.
0,2 ÷ 2,6
1,2
P3.6
PARALLEL SHIFT OF HEATING
CURVE FOR ADD. DIRECT
CIRCUITS
Parallel shift of heating curve for additional heating circuits.
Values 16 ÷ 90 set directly the boiler temperature when additional
direct heating circuit is activated.
-15 ÷ 15 °C
16 ÷ 90 °C
6
Settings for domestic hot water:
Para-
me-
ter
Parameter name
Parameter description
Setting
range
Default
setting
P4.1
D. H. W. TEMPERATURE IN OFF
PERIOD
Setting of d. h. w. temperature in OFF program timer interval.
4 ÷ 70 °C
4
P4.2
PRIORITY OF D. H. W. WARMING
TO CIRCUIT 1
Setting if d. h. w. heating has priority to room heating in circuit 1.
0- NO
1- YES
0
P4.3
PRIORITY OF D. H. W. WARMING
TO CIRCUIT 2
Setting if d. h. w. heating has priority to room heating in circuit 2.
0- NO
1- YES
0
P4.7
TIME PROGRAM FOR D. H. W.
CIRCULATION
Selection of d. h. w. warming time program which will be used for d.
h. w. circulation.
Setting 1 is first time program for domestic hot water warming.
Setting 2 is second time program for domestic hot eater warming.
Setting 3 is selected time program for domestic hot water warming.
1- PROG. 1
2- PROG. 2
3- SELECT.
PROG.
3
Settings for the second heating circuit:
Para-
meter
Parameter name
Parameter description
Setting
range
Default
setting
P2.3
DURATION OF BOOST HEA-
TING
Duration of boosted room temperature by changeover from night to
day heating period.
0 ÷ 200 min
0
P2.4
ROOM TEMPERATURE INCRE-
ASE BY BOOST HEATING
Boost room temperature increase by changeover from night to day
heating period.
0 ÷ 8 °C
3
P2.2
PARALLEL SHIFT OF HEATING
CURVE
Setting of parallel shift of heating curve or calculated stand-pipe
temperature.
Use this setting to eliminate deviation between actual and required
room temperature.
-15 ÷ 15 °C
0