8
REV 7.5.0 / PL-INSTL-TREECOM-EN
PL-M2000-RTU
PL-TREE-COM
ROOT
PL-VC2000
PL-TREE-COM
LEAF
PL-VC2000
PL-TREE-COM
LEAF
PL-C1050
PL-TREE-COM
LEAF
Figure 9
Master Controller with multiple Zone Controllers
(fully wireless network)
Zone Controllers (VC2000, C1050-VAV, T1100) can be connected wirelessly to a Master Unit Controller such as a PL-M2000-HP or RTU
or a PL-C1050-RTU or HP.
1. Each controller must have its own dedicated PL-TREE-COM device
2. The PL-TREE-COM connected to each Zone Controller must be in set as the "LEAF". (NET Port)
3. The PL-TREE-COM connected to the Master Controller must be set as the "ROOT". (NET Port)
4. All PL-TREE-COM modules must have their dipswitches set for the same channel number.