5.  Operational range
 

5a)  The PL-TREE-COM can be oriented in any direction when operating under 200ft of range.

 

5b) The PL-TREE-COM can cover distances up to 2500 ft when oriented properly. 

(Figure 3)

6.  Weatherproof enclosures

  Should a PL-TREE COM module need to be installed outdoors, we recommend installing it in a plastic or resin NEMA 4 type 

 

enclosure, as any metal enclosure will act as a Faraday cage, therefore blocking radio signals.

Figure 3

2,500 ft

Figure 4

 5c)  The PL-TREE-COM radio wave pattern is directional, meaning the signal beam, while able to radiate everywhere, will travel 

   

farther in one specific direction. The built-in antenna is aligned with its front cover (face with the lights and dipswitches). In 

 

 

order to achieve maximum range, or communicate through complex building structure, both PL-TREE COM modules commu-

   

nicating together should have their faceplates facing each other. Signal quality (read at the "LEAF" module) must be at least 

 

 

30% to achieve proper communication. 

(Figure 4)

   NOTE: 

Aligning TREE-COM modules face to face is highly recommended for distances beyond 200 ft.

A signal quality

of at least 30% is

required for proper

communication

Содержание TREE-COM

Страница 1: ...INSTALLING THE TREE COM with Prolon REV 7 5 0 PL INSTL TREECOM EN www proloncontrols com 1 877 977 6566 info proloncontrols com 17510 Rue Charles Suite 100 Mirabel QC J7J 1X9...

Страница 2: ...sor 7 Master Controller with multiple Zone Controllers fully wireless network 8 Master Controller with multiple Zone Controllers wired wireless hybrid network 9 Master Controller with multiple Zone Co...

Страница 3: ...l TREE COM communicating on a given channel must be set with the same dispswitch channel number 3c These dipswitches are not to be mistaken with the controllers Modbus address they are for channel ide...

Страница 4: ...5c The PL TREE COM radio wave pattern is directional meaning the signal beam while able to radiate everywhere will travel farther in one specific direction The built in antenna is aligned with its fr...

Страница 5: ...tion 7c ROOT YELLOW This LED indicates if this device has been set as a ROOT using dipswitch 8 When the LED is ON this device is set as the ROOT for its subnet If the LED is off it is instead a LEAF 7...

Страница 6: ...PL TREE COM device 1 The PL TREE COM connected to the communicating wall sensor must be set as the ROOT 2 The PL TREE COM connected to the Single Zone Unit Controller must be set as the LEAF 3 Both T...

Страница 7: ...portant A PL RS wall sensor CANNOT be connected using a PL TREE COM 1 The PL TREE COM connected to the communicating wall sensor NEEDS to be set as the ROOT INT port 2 The PL TREE COM connected to the...

Страница 8: ...1050 VAV T1100 can be connected wirelessly to a Master Unit Controller such as a PL M2000 HP or RTU or a PL C1050 RTU or HP 1 Each controller must have its own dedicated PL TREE COM device 2 The PL TR...

Страница 9: ...added to the daisy chain to gap the link between the Master and all its zones Figure 10 1 The PL TREE COM on the M2000 Master s side must be connected in the NET port and be set as the ROOT 2 The zone...

Страница 10: ...es regardless of their location within a Prolon network Figure 11 1 The TREE COM that is hardwired to the Modbus Master PL M2000 RTU must be set in ROOT mode 2 The TREE COM hardwired to the follower c...

Страница 11: ...igure 12 1 The PL TREE COM connected to the PL NC2000 via the RS 485 OUT port must be set as the ROOT 2 The PL TREE COM connected to individual PL M2000 or PL C1050 via the INT communication port must...

Страница 12: ...e NFC function must first be enabled on the mobile device 5 The NFC reading may take a few seconds to display Android Once on the settings page hold your phone back of the phone close to the face of a...

Страница 13: ...connecting 1 To scan the TREE COM tap on the settings icon in the left bottom corner 2 Tap on Scan PL TREE COM 3 When ready to detect approach and hold the back of the mobile device very near the powe...

Страница 14: ...nsidered low quality To communicate succesfully with signals in this range it is best to increase the number of retries in Focus PC or mobile app to 10 or 20 attempts so to reduce the likelyhood of fa...

Страница 15: ...eans or translated to another language without prior written consent of Prolon All specifications are nominal and may change as design improvements are introduced Prolon shall not be liable for damage...

Отзывы: