This section describes a two-step installation process in which you install (or mount) 
the thermostat base plate and wire the thermostat.

Inserting the Battery

Insert the battery that is shipped with the thermostat before installing the thermostat 
on the wall. The battery needs to be inserted to ensure the time of the thermostat 
remains accurate during a power outage. See 

Figure 3 on page 9

 for battery location 

and orientation.

Installing the Base Plate

Perform the following steps to mount the thermostat base plate on the wall:

1

Review the 

Installation Guidelines

 on 

page 3

 and position the base plate in an 

appropriate location on the wall. Ensure the location allows you to access and pull the 
wires through the opening in the base plate.

2

Using a pencil, mark the center of the screw holes on the left and right side, and 
bottom center of the base plate.

3

Remove the base plate from the wall and drill two or three holes at the marked 
locations: for drywall, drill 3/16” holes; for plaster, drill 7/32” holes.

4

Gently tap the wall anchors (included in the packaging) into the drilled holes until 
they are flush with the wall.

5

Pull the wires through the base plate and position the base plate over the screw holes. 

6

Attach the base plate to the wall using three 1" screws (included in the packaging).

Wiring the Base Plate Terminals

This section describes how to wire the base plate terminals. Use the instructions in this 
section and refer to:

„

Table 2

 and 

Figure 1 on page 7

 to wire the IMT base plate terminals for Fuel 

Burner HVAC. A Fuel Burner typically burns fossil fuel like oil or gas and does 
not have a wire used as a reversing valve.

„

Table 2

 and 

Figure 2 on page 8

 to wire the IMT base plate terminals for Heat 

Pump HVAC. A Heat Pump configuration always has a wire used to control a 
reversing valve. 

Note

There are four mounting holes on the backplate that allow for mounting in a single 
vertical or horizontal oriented single gang electrical box using only two screws. If 
you are installing the backplate on drywall directly, then use all four screws.

Содержание IMT350c

Страница 1: ...Proliphix Internet Managed Thermostat IMT 350c 350w Installation Guide Release 1 0 Part No 600 03000 350 Rev 1 July 2010...

Страница 2: ...cracked scratched broken or modified plastics other cosmetic damage or parts that have been altered defaced or removed or the scratching cracking or breakage of the product This warranty is not transf...

Страница 3: ...al contact Authorized returns must be shipped prepaid to Proliphix at Proliphix Inc 3 Lan Drive Suite 100 Westford MA 01886 The RMA number must be clearly marked on the outside of the package Products...

Страница 4: ...iv Proliphix Internet Managed Thermostat IMT 350c 350w Installation Guide Release 1 0 Part No 600 03000 350 Rev 1...

Страница 5: ...or from any remote location The c model suffix thermostats can be connected to your network with a CAT5 CAT5E CAT6 Ethernet cable while the w model suffix thermostats support 802 11 b g network conne...

Страница 6: ...to the HVAC system s 24v transformer which is known as the Common By using a wire that is connected to the Common terminal on the transformer you can complete a power circuit and use the 24v HVAC tra...

Страница 7: ...ill with a 3 16 or 7 32 bit Terminal block screw driver included with the thermostat Installation Guidelines Use the following guidelines to install the IMT350 Install the thermostat on an inside wall...

Страница 8: ...wiring You will use these same wires and labels when you connect the IMT See Wiring the Base Plate Terminals page 5 Use the following steps to remove an existing thermostat 1 Turn off power to the en...

Страница 9: ...e and bottom center of the base plate 3 Remove the base plate from the wall and drill two or three holes at the marked locations for drywall drill 3 16 holes for plaster drill 7 32 holes 4 Gently tap...

Страница 10: ...or cooling or reverse for heating in your heat pump Refer to your Heat Pump manual for more information Table 2 Terminal Conversion Chart HVAC Terminal Single Stage Fuel Burner Single Stage Heat Pump...

Страница 11: ...example of a single stage Fuel Burner HVAC system connecting to an IMT base plate Figure 1 Single Stage Fuel Burner HVAC Connections 24VAC Source Fan Control 1st Stage Cool Control 1st Stage Heat Con...

Страница 12: ...stage Heat Pump HVAC system with reverse activate for heat cool connecting to an IMT base plate Figure 2 Single Stage Heat Pump HVAC Connections Common Optional Fan Reverse for Heat Cool W2 RH Y1 G C...

Страница 13: ...l post with the corresponding letter on the IMT base plate For example connect the wire labeled W1 to the W1 terminal post 4 Loosen the terminal post screw used to secure the wires Insert the wire str...

Страница 14: ...nnections To wire the Ethernet network refer to Figure 4 and match the label number to the Proliphix base plate number for CAT5 CAT5E CAT6 color coding Note Only one sensor can be connected to each po...

Страница 15: ...ments for T568A and T568B Table 4 describes the pinout assignments for the T568A and T568B wiring standards Table 5 describes the sensor connectors Table 4 T568A and T568B Pinout Assignments Pin Numbe...

Страница 16: ...scribes what relays are active for the HVAC and fan state Table 6 Relay Matrix W1 W2 Y1 G Fuel Burner Heat1 1h X Xa a If Fan on Heat is enabled Cool1 1c X X Fan X Heat Pump Heat1 1h Xb b If Heat Pump...

Страница 17: ...VAC power source RH or RC is configured to turn on each HVAC system cool heat and fan Most applications use only RH power The Proliphix thermostat is shipped from the factory with the RH and RC jumper...

Страница 18: ...g power to either two EPA 20 or six EPA 60 Proliphix Network Thermostats IMT350c and IMT350w 24VAC is power from the HVAC system which requires RH and C to both be connected to provide power to the th...

Страница 19: ...nt is higher than the temperature reading A flame icon appears within 30 seconds and the HVAC system activates the heat Testing the Cool Controls 1 Verify the HVAC mode is set to either Auto or Cool 2...

Страница 20: ...Beta Draft Confidential 16 Proliphix Internet Managed Thermostat IMT 350c 350w Installation Guide Release 1 0 Part No 600 03000 350 Rev 1 Logging In to the Thermostat...

Отзывы: