3-5. Audible Alarm
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously sounding
Bypass Mode
Sounding every 10 seconds
3-6. Faults Reference Code
Fault event
LED Indicators
Fault event
LED Indicators
Output short circuited LED5 and LED7 on
Overload
LED5 and LED6 on
Inverter abnormal
LED5 and LED4 on
Bus abnormal
LED5, LED8 and LED 9
on
Charger failure
LED5 and LED8 on
High voltage fault
LED5, LED9 and LED10
on
PFC fault
LED5 and LED9 on
Low voltage fault
LED5, LED7, LED8 and
LED 9 on
Boost fault
LED5 and LED10 on
High voltage in
charger
LED5 , LED7, LED8,
LED9 and LED10 on
Temperature abnormal
LED5, LED7 and
LED8 on
Low voltage in
charger
LED5 , LED8, LED9 and
LED10 on
3-7. Warning indicator
Warning
LED (flashing)
Alarm
Input wiring is not connected
correctly
LED1, LED5
Sounding every second
Battery is not connected
LED2, LED5
Sounding every second
Battery fault
LED5, LED9
Sounding every second
Battery overcharging
LED5, LED7, LED8, LED9,
LED10
Sounding every second
Low Battery
LED5, LED7
Sounding every second
Overload
LED5, LED6
Sounding twice every second
Out of bypass voltage range
LED3, LED5
Sounding every second
Charger warning
LED5, LED8
Sounding every second
Other warnings
LED5
Sounding every second
Содержание PRO900-VL
Страница 1: ...ONLINE UPS User Manual PROFESSIONAL I SERIES 1P 1P TOWER PRO900 VS VL 1 3KVA Version 1 00 English ...
Страница 8: ...6 Not in use For Rack Type Models Only ...
Страница 9: ...7 Not in use For Rack Type Models Only ...
Страница 10: ...8 Not in use For Rack Type Models Only ...
Страница 14: ...12 2 5 Battery replacement Only for Rack UPS ...
Страница 15: ...13 2 6 Battery kit assembly Option for Rack UPS ...
Страница 16: ...14 Not in use For Rack Type Models Only ...