7 - DMX CONNECTION
CONNECTION OF THE CONTROL SIGNAL: DMX LINE
The product has XLR sockets for DMX input and output.
The default pin-out on both socket is as the following diagram:
Fig. 05
Pin1 : GND - Shield
Pin2 : - Signal
Pin3 : + Signal
Pin4 : N/C
Pin5 : N/C
DMX - OUTPUT
XLR socket
DMX - INPUT
XLR plug
INSTRUCTIONS FOR A RELIABLE DMX CONNECTION
Use shielded twisted-pair cable designed for RS-485 devices: standard microphone cable cannot trans-
mit control data reliably over long runs. 24 AWG cable is suitable for runs up to 300 meters (1000 ft).
Heavier gauge cable and/or an amplifier is recommended for longer runs.
To split the data link into branches, use splitter-amplifiers in the connection line.
Do not overload the link. Up to 32 devices may be connected on a serial link.
CONNECTION DAISY CHAIN
Connect the DMX data output from the DMX source to the product DMX input (male connector XLR)
socket.
Run the data link from the product XLR output (female connector XLR) socket to the DMX input of the
next fixture.
Terminate the data link by connecting a 120 Ohm signal termination. If a splitter is used, terminate
each branch of the link.
Install a DMX termination plug on the last fixture on the link.
CONNECTION OF THE DMX LINE
DMX connection employs standard XLR connectors. Use shielded pair-twisted cables with 120Ω im-
pedance and low capacity.
The following diagram shows the connection mode:
Fig. 06 - Example 25 DMX channels configuration
. . . . . . . . . . . .
DMX Address: 33
DMX Address: 108
DMX Address: 58
DMX Address: 83
. . . . . . . . . . . .
DMX512 Controller
DMX IN
DMX IN
DMX IN
DMX IN
DMX OUT
DMX OUT
DMX OUT
DMX OUT