3.2 Wiring
Wiring Size
:
DC cables must be sized to carry the maimum full load current and not to exceed the system
volt drop requirements. The following cable sized are recommended. When running wires,
if they pass through panels or wall, ensure the wires are protected from damage by sharp
edges. The use of cable glands is recommended.
Current
0-5A
5-10A
10-15A
15-20A
20-25A
25-35A
Minimum cable Size
1.0mm or 18 AWG
2.0mm or 14AWG
3.0mm or 13AWG
4.0mm or 11AWG
5.0mm or 10AWG
6.0mm or 9 AWG
3.1 Configuration
SIDE PANEL
1
2
146,9
70
70
3 4 5 6 7 8 9
10
11
No.
Label
Definition
Description
1
POWER
2
3
4
6
5
7
8
9
10
11
Starter Bat+
Starter battery connector
Service battery connector
Centralized output connector
Separated DC outputs connector
Starter Bat-
Connect to starter
Connect to starter battery-
Service Bat+
Service Bat-
Load+
Load-
L1+
→
L10+
L1-
→
L10-
Connect to service
Connect to service battery-
Connect to DC load+
Connect to DC load+
Connect to DC load-
Connect to DC load-
AC input port
Mode selection switch
Load switch connector
Load Switch
Power supply or charger mode
Connect external switch
OFF/Charger
ON/
Power supply