CLEANING GUIDE FOR OUTDOOR HEAT EXCHANGERS 

 

1.

 

GENERAL RULES 

 

It is strongly recommended to regularly clean coil of the heat exchanger, at least once a year. Insufficiently maintained 
equipment will have a short life expectancy, compared with an identical equipment with regular routine maintenance. 
An insufficiently maintained equipment exposed to an aggressive environment, may be quickly deteriorated, even if an 
appropriate protective treatment has been applied for the manufacturing of equipment. 
The purpose of the cleaning is to get rid of all the hydroscopic crystals as well as deposits of all kinds. 
Depending on the environmental and operating conditions, it may be necessary to increase the frequency of cleaning, 
particularly depending on: 
- operating time of the fans 
- quality of the surrounding air (proximity to sea, factories, relative humidity, ...) 
- presence of adiabatic ramps 
The frequency of the cleaning operations is mainly function of the conditions of use and of the amount of the deposits. That's 
why, it is recommended to regularly carry out a visual inspection of the exchanger in order to start a cleaning operation as soon 
as necessary. 
A late cleaning : 
- will take longer time to achieve 
- will be more complex to achieve 
- reduces the life expectancy of the exchanger 
 
 

Below, 3 pictures of exchangers at different states of soiling (photos given as an indication). 
 
 
 

 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Turn off the entire unit, and secure the unit against unintentional power-on. 
Comply with the site's specific safety instructions. 
 

For heat exchangers with BLYGOLD® or HERESITE® coating, refer to the paragraph specific to each treatment. 
 
If the fins are damaged, it is necessary to straighten them with an appropriate tool before starting a cleaning procedure. 

 

 

Содержание CONDENSEURS

Страница 1: ...1 CLEANING GUIDE FOR OUTSIDE HEAT EXCHANGERS CONDENSEURS GASCOOLERS DRYCOOLERS...

Страница 2: ...TIONS FOR OUTDOOR HEAT EXCHANGERS 3 1 GENERAL RULES 3 2 LOW PRESSURE CLEANING SLIGHTLY SOILED COILS 4 3 HIGH PRESSURE CLEANING MODERATELY SOILED COILS 6 4 HEAT EXCHANGERS WITH BLYGOLD COATING 6 5 HEAT...

Страница 3: ...e of the fans quality of the surrounding air proximity to sea factories relative humidity presence of adiabatic ramps The frequency of the cleaning operations is mainly function of the conditions of u...

Страница 4: ...ter out of the heat exchanger before proceeding on the heat exchanger then start cleaning at a distance greater than the recommended minimum distance then move closer gradually When using hot water th...

Страница 5: ...surface Orient the water jet perpendicularly to the exchanger An angled position will cause the fins to fold Make sure not to orient the jet towards the fans it is mandatory to protect the fans again...

Страница 6: ...it is mandatory to protect the fans against splashing water Repeat this operation as necessary until you obtain a perfectly clean surface When using cleaning agents other than water choose a neutral p...

Страница 7: ...r maintenance on heat exchangers coated with HERESITE treatment please refer to SAKAPHEN INSTRUCTION TECHNIQUE INS TEC 18 procedure attached below It is an obligation to respect the distance and water...

Страница 8: ...8...

Отзывы: