INSTALLATION 

 

 

Page 7 

 

INLET & OUTLET 

 

 

In case of  high concentration of  impurities  in the  inlet 

water, we recommend the installation of a sediment filter, 
ahead of the appliance. 

 

 

We  strongly  recommend  the  use  of  flexible  hoses  to 

connect the appliance to the water distribution system; use 
hoses with a  large diameter in order to limit the  pressure 
loss. 

 

 

We  strongly  recommend  the  installation  of  a  bypass 

system  (not  included  with  this  product!)  to  isolate  the 
appliance  from  the  water  distribution  system  in  case  of 
repairs. It allows to turn off the water to the appliance, while 
maintaining full-flow (untreated) water supply to the user. 
 

with factory bypass (optional) 

 

  

Picture 2

 

 = mains water supply (untreated water) 

 = inlet of control valve (untreated water) 

 = outlet of control valve (treated water) 

 = application (treated water) 

1.

 

Screw  the  factory  bypass  onto  the  in/out  ports  on  the 
control  valve  (

&

);  make  sure  to  install  the  gasket 

seals. Tighten the nuts firmly by hand. 

2.

 

Screw  the  connection  kit  with  nuts  onto  the  factory 
bypass  (

&

);  make  sure  to  install  the  gasket  seals. 

Tighten the nuts firmly by hand. 

3.

 

Connect  the  mains  water  supply  to  the  adaptor  on  the 
inlet port of the factory bypass (

). 

4.

 

Connect the application to the adaptor on the outlet port 
of the factory bypass (

). 

 

with 3-valve connection kit (not included) 

 

  

Picture 3

 

 = inlet of control valve (untreated water) 

 = outlet of control valve (treated water) 

1.

 

Install the 3-valve connection kit. 

2.

 

Screw the connection kit with nuts onto the in/out ports 
on  the  control  valve  (

&

);  make  sure  to  install  the 

gasket seals. Tighten the nuts firmly by hand. 

3.

 

Connect the IN valve of the 3-valve connection kit to the 
adaptor on the in port of the control valve (

). 

4.

 

Connect the OUT valve of the 3-valve connection kit to the 
adaptor on the out port of the control valve (

). 

5.

 

Connect the mains water supply to the inlet of the 3-valve 
connection kit. 

6.

 

Connect  the  application  to  the  outlet  of  the  3-valve 
connection kit. 

 
 
 
 
 
 
 
 
 
 
 
 

DRAIN

 

 

 

We recommend the use of a stand pipe with P-trap.  

 

 

To prevent backflow from the sewerage system into the 

appliance, always ensure sufficient air gap between the end 
of the drain hose or pipe and the sewerage system. 

 

 

Always use separate drain hoses for the control valve(s) 

(discharge of rinse water) and the brine tank overflow. 

 

 

Lay-out the drain hoses in such a way that pressure loss 

is minimized; avoid kinks and unnecessary elevations. 

 

 

Make sure that the sewerage system is suitable for the 

rinse water flow rate of the appliance. 
 

for PF-MMX 

 

  

Picture 4

 

1.

 

Connect the 19 mm hose to the drain connection of the 
control valve (

); secure it by means of the clamp. 

2.

 

Run the drain hose to the sewerage system and connect 
it, ensuring sufficient air gap between the end of the hose 
and the sewerage system. This drain line operates under 
pressure, so it may be installed higher than the appliance. 

PF-BTA: brine tank assembly (optional) 

1.

 

Connect  the  19  mm  hose  to the overflow elbow  on  the 
brine tank; secure it by means of the clamp. 

2.

 

Run the drain hose to the sewerage system and connect 
it, ensuring sufficient air gap between the end of the hose 
and  the  sewerage  system.  This  drain  line  does  NOT 
operate under pressure, so it may NOT be installed higher 
than the brine tank. 

 

Содержание PF-BTA

Страница 1: ...2019 erie water treatment TM EN PF MMX Rev2019 03 Technical Manual MULTI PURPOSE WATER FILTER Models PF MMX PF BTA...

Страница 2: ...ic control panel Page 9 Maintenance Page 13 Troubleshooting Page 14 Electrical wiring diagram Page 16 Default configuration parameter settings Page 17 Composition overview Page 18 Exploded view PF MMX...

Страница 3: ...nly be undertaken by a competent person aware of the local codes in force All plumbing and electrical connections must be done in accordance with local codes Before setting up the appliance make sure...

Страница 4: ...below the minimum OPERATING TEMPERATURE MIN MAX 2 48 C 35 120 F do not install the appliance in an environment where high ambient temperatures e g unvented boiler house or freezing temperatures can oc...

Страница 5: ...ith the optional Wi Fi function indicate this by adding W to the corresponding part number PN 35810 Softener 1 Simplex 25L PN 35810 W Softener 1 Simplex 25L Wi Fi enabled 2400VS J4JB PRL1 Control Valv...

Страница 6: ...n 6 Unplug the top of the riser tube CONTROL VALVE 1 Make sure the O ring in the riser insert and the tank O ring around the threaded section of the control valve are in the correct position 2 Screw t...

Страница 7: ...ve make sure to install the gasket seals Tighten the nuts firmly by hand 3 Connect the IN valve of the 3 valve connection kit to the adaptor on the in port of the control valve 4 Connect the OUT valve...

Страница 8: ...N valve 6 After 2 3 minutes open a cold treated water faucet nearby the appliance and let the water run for a few minutes until all air is purged fromthe installation and the filter media is rinsed it...

Страница 9: ...ppen 1 the display will intermittently show the message 2 the buzzer if enabled see Basic Settings will beep 3 times every 5 minutes While the appliance will continue to operate normally it is recomme...

Страница 10: ...r down button to activate the holiday mode by setting the number of full days away from home or deactivate the holiday mode OFF Once the control panel is back in service mode the display will show The...

Страница 11: ...TIONS CONFIGURATION PARAMETERS Before entering the programming mode make sure that the appliance is in the service mode All configuration parameters on this appliance have been pre programmed in the f...

Страница 12: ...ayed regeneration at the programmed time of regeneration is started 10 Press the scroll button again the display will show only when the regeneration mode is set to Delayed or Dlyd Immd Press the up o...

Страница 13: ...s number of regenerations since installation TotVol total volume of treated water since installation LastRgn consumed capacity at last regeneration InstFlow instantaneous flow rate through appliance A...

Страница 14: ...appliance needs brine for its periodic regenerations This brine solution is made from water that is automatically dosed in the brine tank by the control valve and water conditioner salt The user shou...

Страница 15: ...Page 15...

Страница 16: ...roblem Excessive water in brine tank Appliance regenerates too frequently Verify program Excessive water in brine tank Control valve fails to draw brine Refer to problem Control valve fails to draw br...

Страница 17: ...k in brine line Verify brine line and connections for air leakage No water in brine tank Refer to problem Control valve fails to refill brine tank Control valve cycles continuously Defective micro swi...

Страница 18: ...ition switches flow meter power lead drive motor auxilliary contacts 24 VDC max 500mA AUX1 PF SOF1 SIM service valve NO optional PF SOF1 PRL service valve NO PF SOF1 ALT service valve NC AUX2 PN 74372...

Страница 19: ...cle 2 BRINE DRAW SLOW RINSE min 57 50 78 88 Cycle 3 FAST RINSE REFILL min 2 4 6 4 6 Regen Dlyd Immd Dlyd Immd Dlyd Immd Dlyd Immd Regen 2 00 2 00 2 00 2 00 Rsrv Variable Variable Variable Variable Aux...

Страница 20: ...transformer 1 BSP male connections Pressure tank incl distributor assy Filter media 12 kg bag Ltr model model PF MMX 24 35690 2400VS J4JB PRL1 1 10x35 1 2 36 35691 2400VS J1JB PRL1 1 10x47 1 3 48 356...

Страница 21: ...E Page 21...

Страница 22: ...EXPLODED VIEW PF MMX SYSTEM Page 22...

Страница 23: ...e assembly to be cut to length 20mm below pressure tank opening 4 74312 Transformer 100 230 24 VDC 50Hz 1 0A EuroT plug 74313 Transformer 100 230 24 VDC 50Hz 1 0A UK plug 5 287 166 Top distributor 6 2...

Страница 24: ...EXPLODED VIEW PF MMX TIMER ASSEMBLY Page 24...

Страница 25: ...15 222 Screw drive motor assembly 2x 12 74267 Cable clamp 13 70312 Strain relief power lead 14 74370 Socket cable assembly InterConnect 24 VDC 15 72261 Drive motor 16 75156 Worm drive shaft 17 70965...

Страница 26: ...EXPLODED VIEW PF MMX VALVE BODY Page 26...

Страница 27: ...o 21 185 007 6 O ring mixing valve 22 568 406 Mixing valve 23 186 118 O ring sleeve 24 568 407 L Sleeve mixing valve 25 568 385 2 B Refill Flow Control 1 9 ltr min 24 Ltr 36 Ltr 568 385 2 D Refill Flo...

Страница 28: ...125 BP 0275 01 Brine platform for simplex BT 0275 6 BW4 072 Brine well 10 cm 72 cm BT 0125 BW4 088 Brine well 10 cm 88 cm BT 0275 7 H4500 48 Air check to be cut to length 8 H4640 32 Float 9 Grommet fl...

Страница 29: ...inse water usage per regeneration ltr 202 246 348 522 Max flow to drain ltr min 9 8 9 8 15 1 22 7 Dimensions Model PF MMX Filter media ltr 24 36 48 72 Width mm W 264 264 311 365 Depth mm D 282 282 311...

Страница 30: ...s Model PF BTA Volume ltr 125 275 Diameter mm D 540 685 Height mm H 850 975 Height overflow mm H1 660 825 Max salt storage capacity kg 100 200 Model PF BTA Volume ltr 125 275 Hydraulic connection brin...

Страница 31: ...Page 31...

Страница 32: ...erie water treatment a division of Aquion Inc www eriewatertreatment com...

Отзывы: