      PROFIRE PID Operator Guide

 

 

PROFIRE 
1.855.776.3473 
[email protected] 

 

Page 4 of 7 

 

Once highlighted, press the 

 key to access the appliance 

Status

 screen 

 

The appliance 

Status

 screen displays the core data vital to the system such as the operating temperatures, 

inputs, outputs, and the state of the burner(s) connected to the appliance. 

Key Points 

These are some of the key things to look for from the appliance 

Status

 screen: 

State of the Controller(s) 

Ensure that all controllers are running in a steady state. In the example above (

Burner FF

), the state of the 

controller is listed as 

Low Fire

 

which is a steady state. 

High Fire

 

and 

Pilot

 can also be acceptable steady states. 

Outlet Temperature 

The outlet temperature should be stable (not fluctuating) and reading at the established setpoint. 

Firing Rate 

The Firing Rate should be stable and not wildly fluctuating. 

Alerts Tab 

There should be 

no

 asterisk next to the 

Alerts

 tab. If there is an asterisk (as pictured here:  

), then 

navigate to the 

Alerts

 tab and refer to the PF3100 Product Manual or contact your supervisor. 

Any further investigation of the system requires understanding which mode the PID Staging is in. This can be 
found  by  accessing  the 

Settings

  tab,  navigating  to 

Process  Control

,

 

and  then 

Advanced  PID  Config

 

and 

observing which mode is selected in the 

PID Staging Mode

 

setting. Please refer to Section 2 -  PID Staging 

Modes below for a detailed review of the modes. Once the mode is known, the PID Status can be identified. 

 

 

Содержание PF3100 Series

Страница 1: ...PROFIRE PID Operator Guide PID Staging November 2017 PROFIRE 1 855 776 3473 solutions profireenergy com Page 1 of 7 PROFIRE PID Operator Guide PID Staging...

Страница 2: ...icator light as seen below Starting an appliance If the system is not running select the appliance using the key From the appliance Status screen check that there is no asterisk next to the Alerts tab...

Страница 3: ...ure should be noted If the outlet temperature is at its setpoint or within a reasonable tolerance of the setpoint then most likely the system is performing as expected This guide will help highlight w...

Страница 4: ...an also be acceptable steady states Outlet Temperature The outlet temperature should be stable not fluctuating and reading at the established setpoint Firing Rate The Firing Rate should be stable and...

Страница 5: ...solutions profireenergy com Page 5 of 7 PID Status The status of the PID can be determined by first selecting the controller in this example Burner FF Hitting the key will bring up this table and dis...

Страница 6: ...do the opposite For example if the input is open the PID Status will state Secondary Control and if the input is closed the PID Status will state Primary Control Primary in Range When the Primary Tem...

Страница 7: ...ormation If you have any concerns or questions about this information please contact PROFIRE as follows U S 1 801 796 5127 321 South 1250 West Suite 1 Lindon UT 84042 USA solutions profireenergy com C...

Отзывы: