Profibus T1H-PBC Скачать руководство пользователя страница 3

It is important to understand the installa-
tion requirements for your Terminator I/O 
system. This will ensure that the Terminator 
I/O products work within their environ-
mental and electrical limits.

Plan for safety

This catalog should never be used as a 
replacement for the technical data sheet 
that comes with the products or the 

 

T1K-INST-M Installation and 
I/O Manual (available online at 

 

.) The tech

-

nical data sheet contains information that 
must be followed. The system installation 
should comply with all appropriate elec-
trical codes and standards.

Unit dimensions and 

mounting orientation

Use the following diagrams to  decide 
if the Terminator I/O system can be 
installed in your application. Terminator 
I/O units should be mounted horizon-
tally. To ensure proper airflow for cooling 
purposes, units should not be mounted 
upside-down. It is important to check the 
Terminator I/O  dimensions against the 
conditions required for your application. 
For example, it is recommended to leave 
2” depth for ease of access and cable 
clearance. However, your distance may 
be greater or less. Also, check the instal-
lation guidelines for the recommended 
cabinet clearances.

48mm

(1.89in)

80mm

(3.15in)

80mm

(3.15in)

48mm

(1.89in)

80mm

(3.15in)

48mm

(1.89in)

89mm

(3.5in)

80mm

(3.15in)

83.3mm

(3.28in)

Power Supply

Network Interface Module

Half-size I/O Module 

with Base

System Depth

Full-size I/O Module 

with Base

Dimensions and Installation

 

See the Enclosures 

section for an enclosure that may 

be suitable for your application

Terminator I/O Environmental Specifications

Ambient Operating Temperature

32°F to 131°F (0°C to 55°C)

Storage Temperature

-4°F to 158°F (-20°C to 70°C)

Ambient Humidity

5% to 95% (Non-condensing)

Atmosphere

No corrosive gases. The level of environmental  

pollution = 2   (UL 840)

Vibration Resistance

MIL STD 810C, Method 514.2

Shock Resistance

MIL STD 810C, Method 516.2

Voltage Withstand (Dielectric)

1500VAC, 1 minute

Insulation Resistance

500 VDC, 10 M

q

Noise Immunity

NEMA  ICS3-304 

Impulse noise 1µs, 1000V 

FCC class A 

RFI (144MHz, 430MHz  10W, 10cm)

Agency Approvals

UL, CE, FCC class A, NEC Class 1 Division 2

tFED-53

Universal Field I/O

.

Содержание T1H-PBC

Страница 1: ...Terminator I O modules and for controlling them with a PROFIBUS master Using our PROFIBUS I O sub system will increase installation flexibility as well as save on wiring costs The T1H PBC module supports all Terminator discrete and analog I O modules The T1H PBC also offers the following features Cost effective With a single network for devices hardwiring costs are reduced Easy connectivity Low co...

Страница 2: ...n vertical connector 9 pin male D sub Terminator I O T1H PBC or any PROFIBUS ISA PCI Personal Computer Master Slave Card Terminator I O Modules Supported Discrete Types Analog Types 8 point DC Input 8 channel Current Input 8 point AC Input 8 channel Voltage Input 16 point DC Input 8 channel Current Output 16 point AC Input 8 channel Voltage Output 8 point DC Output 16 channel Current Input 8 point...

Страница 3: ...ple it is recommended to leave 2 depth for ease of access and cable clearance However your distance may be greater or less Also check the instal lation guidelines for the recommended cabinet clearances 48mm 1 89in 80mm 3 15in 80mm 3 15in 48mm 1 89in 80mm 3 15in 48mm 1 89in 89mm 3 5in 80mm 3 15in 83 3mm 3 28in Power Supply Network Interface Module Half size I O Module with Base System Depth Full si...

Страница 4: ...lation Terminator I O modules feature separate terminal bases for easy installation To install I O modules 1 Slide the module into its terminal base until it clicks into position 2 Hook upper DIN rail tabs over the top of DIN rail and press the assembly firmly onto the DIN rail 3 Slide the module along the DIN rail until it engages with the adjacent module DN ASB 1 angled mounting bracket Optional...

Страница 5: ...al Block Phoenix Contact MVSTBW 2 5 4 ST 5 08 BK MVSTBW 2 5 6 ST 5 08 BK Note 500mA 24VDC can be achieved by lowering the 5VDC from 2000mA to 1500mA Power Budget Example Module 5VDC 24VDC T1K 01AC 2000mA 300mA T1H EBC100 300mA 0mA T1K 16ND3 70mA 0mA T1K 16TD2 200mA 0mA T1F 08AD 1 75mA 50mA Remaining 1355mA 250mA Module 5VDC 24VDC Analog Input Modules T1F 08AD 1 75 50 T1F 08AD 2 75 50 T1F 16AD 1 75...

Страница 6: ... base A maximum of one T1K 05CBL RR cable can be used per expansion system Note When this cable is used the expan sion I O assignments are from right to left reversed Note The 1 versions of the expansion cables pass 24VDC through on an isolated wire All cables pass the 5VDC base power Any local expansion DC input module configured for internal power current sourcing must either have a power supply...

Страница 7: ... it easy to wire 2 and 3 wire devices ensuring clean wiring with only one wire per termination External user supplied 24VDC power or auxiliary 24VDC terminals from T1K 01AC can be easily applied directly to one end of the terminal rows and jumpered across each base in the system This is a convenient solution for powering analog I O and discrete DC output devices whose modules do not have direct ac...

Отзывы: