Profibus T1H-PBC Скачать руководство пользователя страница 1

T1H-PBC          

PROFIBUS

TM

 I/O 

system overview

If you are using a PROFIBUS™ controller 
network, the Terminator I/O sub-system 
will help further reduce the cost of your 
overall application. The T1H-PBC module 
allows the micro-modular Terminator I/O 
sub-system to be linked with a PROFIBUS

 

master controller. PROFIBUS is a control 
bus that provides a common method 
to connect automation equipment with 
devices on a single network. This standard 
communications media is referred to as 
PROFIBUS and significantly reduces hard-
wiring costs. PROFIBUS

 

provides specifica-

tions for information exchanged between 
nodes, such as controller data associated 
with low- level device and configuration 
parameters individually related to system 
operations.

PROFIBUS allows 32 stations per segment. 
Segments vary in length depending on 
the desired transmission speed. The 
maximum speed is achieved on a segment 
100 meters (327 feet) in length. Our 
PROFIBUS-DP Slave represents a single 
station. Repeaters also count as stations 
and are used to extend the network to 
greater distances. Our PROFIBUS module 
supports baud rates of 9.6 Kbaud to 12 
Mbaud depending on the network length. 

Here’s how it works:

The T1H-PBC module is a PROFIBUS 
slave, which can be plugged into 
the network interface position of the 
Terminator I/O micro-modular family of 
I/O bases. This module reports all the 
identification data, diagnostic information, 
and parameters that control the module 
operation. The T1H-PBC module scans 
and reports all discrete and analog I/O 
data to a PROFIBUS  master. The exter-
nally-powered AC  Terminator I/O base 
units contain a 24VDC power supply for 
simple wiring of sensors and actuators 
into the Terminator I/O modules, and for 
controlling them with a PROFIBUS master. 
Using our PROFIBUS I/O sub-system 
will increase installation flexibility as well 
as save on wiring costs. The T1H-PBC 
module supports all Terminator discrete 
and analog I/O modules.

The T1H-PBC also offers the following 
features:

•  

Cost-effective: 

With a single network for 

devices, hardwiring costs are reduced.

•  

Easy connectivity:

 Low-cost installation is 

easy to implement and maintain.

   Diagnostics:

 The PROFIBUS slave offers 

advanced error diagnostics not commonly 

available in traditional systems.

•    

High baud rates:

 Response time is 10 ms 

per device

•  

LED Indicators:

 These provide quick indi-

cation of Terminator power and operating 

mode.

Profibus Base Controller

MODULE STATUS

LINK ACTIVE

LINK GOOD

ERROR

P

R

O

F

I

B

U

S

 

P

O

R

T

PROFIBUS™ Slave

Specifications

Module Type

PROFIBUS

 Network Interface Module

Max. Expansion

126 stations, 32 stations per segment, 9 repeaters in a row

Max. I/O Points per Controller

244 Input Bytes (analog or discrete) 

244 Output Bytes (analog or discrete) 

as specified by the PROFIBUS DP Specification

Communications 

RS-485 PROFIBUS, PROFIBUS-DP. 

Baud rate selectable from 9.6 Kbaud to 12 Mbaud. 

Module Connectors

PROFIBUS 9-pin D-shell, RJ-12 serial (for firmware update only)

Internal Power Consumption

530mA maximum at 5VDC (supplied by base power supply)

Operating Environment

0ºC to 60ºC (32ºF to 140ºF), 5% to 95% humidity  

(non-condensing)

Manufacturer

Host Automation Products, L.L.C.

Please Note:

1.   Terminator I/O PROFIBUS slave network interface mod-

ule T1H-PBC is a PTO-certified PROFIBUS-compliant 

slave I/O interface product.  

See www.profibus.com for more information.

2   For use with Think & Do Software, we recommend the 

SST PROFIBUS PCI Master Card, part number  

5136-PFB-PCI. (AutomationDirect does not provide this 

interface).  

See www.mysst.com for more information.

tFED-61

Universal Field I/O

.

Содержание T1H-PBC

Страница 1: ...Terminator I O modules and for controlling them with a PROFIBUS master Using our PROFIBUS I O sub system will increase installation flexibility as well as save on wiring costs The T1H PBC module supports all Terminator discrete and analog I O modules The T1H PBC also offers the following features Cost effective With a single network for devices hardwiring costs are reduced Easy connectivity Low co...

Страница 2: ...n vertical connector 9 pin male D sub Terminator I O T1H PBC or any PROFIBUS ISA PCI Personal Computer Master Slave Card Terminator I O Modules Supported Discrete Types Analog Types 8 point DC Input 8 channel Current Input 8 point AC Input 8 channel Voltage Input 16 point DC Input 8 channel Current Output 16 point AC Input 8 channel Voltage Output 8 point DC Output 16 channel Current Input 8 point...

Страница 3: ...ple it is recommended to leave 2 depth for ease of access and cable clearance However your distance may be greater or less Also check the instal lation guidelines for the recommended cabinet clearances 48mm 1 89in 80mm 3 15in 80mm 3 15in 48mm 1 89in 80mm 3 15in 48mm 1 89in 89mm 3 5in 80mm 3 15in 83 3mm 3 28in Power Supply Network Interface Module Half size I O Module with Base System Depth Full si...

Страница 4: ...lation Terminator I O modules feature separate terminal bases for easy installation To install I O modules 1 Slide the module into its terminal base until it clicks into position 2 Hook upper DIN rail tabs over the top of DIN rail and press the assembly firmly onto the DIN rail 3 Slide the module along the DIN rail until it engages with the adjacent module DN ASB 1 angled mounting bracket Optional...

Страница 5: ...al Block Phoenix Contact MVSTBW 2 5 4 ST 5 08 BK MVSTBW 2 5 6 ST 5 08 BK Note 500mA 24VDC can be achieved by lowering the 5VDC from 2000mA to 1500mA Power Budget Example Module 5VDC 24VDC T1K 01AC 2000mA 300mA T1H EBC100 300mA 0mA T1K 16ND3 70mA 0mA T1K 16TD2 200mA 0mA T1F 08AD 1 75mA 50mA Remaining 1355mA 250mA Module 5VDC 24VDC Analog Input Modules T1F 08AD 1 75 50 T1F 08AD 2 75 50 T1F 16AD 1 75...

Страница 6: ... base A maximum of one T1K 05CBL RR cable can be used per expansion system Note When this cable is used the expan sion I O assignments are from right to left reversed Note The 1 versions of the expansion cables pass 24VDC through on an isolated wire All cables pass the 5VDC base power Any local expansion DC input module configured for internal power current sourcing must either have a power supply...

Страница 7: ... it easy to wire 2 and 3 wire devices ensuring clean wiring with only one wire per termination External user supplied 24VDC power or auxiliary 24VDC terminals from T1K 01AC can be easily applied directly to one end of the terminal rows and jumpered across each base in the system This is a convenient solution for powering analog I O and discrete DC output devices whose modules do not have direct ac...

Отзывы: