PROFIBUS USER MANUAL Leine & Linde AB
Part Id: 740590-01
34
Document Id: 740590 Ver. 01
Publication date: 2010-06-01
DDLM_Slave_Diag
Octet
20
21
Bits
15 – 8
7 – 0
WARNINGS
Bits Definition
= 0
= 1
0 Frequency
exceeded No
Yes
1 Temperature
exceeded No
Yes
2
Light control reserve
Not reached
Reached
3
CPU monitoring status
OK
Reset
4 Maximum
operating
time
exceeded
No Yes
5 Battery
charging
OK
Too
low
6
Reference point
Reached
Not reached
7
Currently
not
assigned
•
15
Table 29 Diagnostics, warnings
5.6.10 Supported Warnings
The diagnostic octets 22 and 23 contain information on supported warnings.
DDLM_Slave_Diag
Octet
22
23
Bits
15 – 8
7 – 0
Supported
Warnings
Bits Definition
= 0
= 1
0
Frequency warning
Not supported
Supported
1
Temperature warning
Not supported
Supported
2
Light control reserve
warning
Not supported
Supported
3
CPU monitoring status
warning
Not supported
Supported
4 Maximum
operating
time
exceeded warning
Not supported
Supported
5 Battery
charging
warning Not supported
Supported
6
Reference point warning Not supported
Supported
7
Currently
not
assigned
•
15
Table 30 Diagnostics, supported warnings