MAIN FEATURES, FUNCTIONS WITH REQUIREMENT AND ACCESSORY FUNCTIONS.
•
Integrated, single-zone (1 zone max) voice alarm system, with class D power amplifiers and power supply unit with primary source
(230Vac network) and backup source (48Vdc batteries).
•
ARM Cortex M3 processor, DSP 16bit 48Khz.
•
Controlled dynamic microphone on front panel; microphone capsule continuity monitoring, cable cut and short-circuit
•
Key or password to access the machine functional levels
•
Alarm and generic messages, recorded on uSD card. Contents monitored by system processor.
•
Class D power amplifiers, power 300W
•
2 Speaker lines (line A and line B) with 100V constant voltage with transformer coupling
•
Independent monitoring of the speaker lines (A+B) with direct measurement of AC voltage and current at 18Khz and FFT analysis.
•
2 Contact inputs with line monitored for alarm message activation (interruption and cable cut)
•
8 contact inputs (not monitored) to activate generic and service messages
•
3 Normally Open output contacts “Relay” for reporting the machine status: VOICE ALARM / FAULT WARNING / SYSTEM DISABLEMENT.
•
Input for remote emergency microphone workstation with monitored connection.
•
Input for generic microphone workstation for service messages.
•
RS485 port (reserved for future use)
•
Ethernet port for remote communication (reporting of status, configuration, audio streams).
•
Power supply unit according to Standard EN54-4 with main source (230Vac); backup source (48Vdc battery); temperature, battery
impedance and battery charger status monitoring.
•
Comprehensive user interface for a straightforward configuration
The following figure schematically shows the connections outside the system.
VA 301
Postazione
di chiamata
Postazione
di Emergenza
Sorgente Sonora
LINEA A
Contatto Allarme
Contatto Evacuazione
LINEA B
CENTRALE
ANTI INCENDIO
SUBWOOFER
Attivo
Contatti Fault/Alarm/Disablement
RS 485
Ethernet
8x Contatti per messaggi generici
Call
workstation
Emergency
workstation
FIRE-FIGHTING
STATION
Alarm Contact
Evacuation Contact
Fault/Alarm/Disablement Contacts
8 Contacts for generic messages
Sound Source
LINE A
LINE B
External
Amplifier
AE300