Procom GHBVL50 Скачать руководство пользователя страница 17

17

Ignition Control LED

The ignition control board contains a green LED which indicates the following:

TABLE 3

IGNITION CONTROL LED

TABLE 4

NATURAL GAS MANIFOLD PRESSURES − inch w.g. (kPa)

TABLE 5

LP/PROPANE GAS MANIFOLD PRESSURES − inch w.g. (kPa)

LED

UNIT OPERATION

Slow. Flash*

Normal Operation − No call for heat

Fast Flash

Normal Operation − Call for heat

2 Flashes

System lockout − failed to detect or sustain flame

 

3 Flashes

Pressure switch failed closed before CAI is 

energized or failed open after CAI is energized

4 Flashes

High limit or rollout switch open

5 Flashes

Flame sensed and gas valve not energized

Steady Off

Loss of Power

Steady On

Ignition control failure

*

When thermostat is placed in continuous fan mode LED will slowly flash.

High Altitude Adjustments

Units may be fired at full input up to 2000 feet. (610m) above sea level. Above 2000 feet 

(610m), manifold pressure must be adjusted on some units. Adjust pressure regulator to 

pressure shown in table 4 for natural gas and table 5 for LP/propane gas.

INPUT

(BTU/Hr)

Altitude in Feet (Meters)

0−3500

(0−1067)

35−4500

(1067−1372)

45−5500

(1372−1676)

55−6500

(1676−1981)

65−7500

(1981−2286)

50

3.5 (0.87)*

3.5 (0.87)*

3.5 (0.87)*

3.5 (0.87)*

3.4 (0.85)

80

3.5 (0.87)*

3.4 (0.85)

3.3 (0.82)

3.2 (0.80)

3.1 (0.77)

*No adjustment required.

INPUT

(BTU/Hr)

Altitude in Feet (Meters)

0−3500

(0−1067)

35−4500

(1067−1372)

45−5500

(1372−1676)

55−6500

(1676−1981)

65−7500

(1981−2286)

50

9.5 (2.37)*

9.5 (2.37)*

9.5 (2.37)*

9.5 (2.37)*

9.2 (2.28)

80

9.5 (2.37)*

9.2 (2.28)

8.9 (2.21)

8.6 (2.13)

8.3 (2.06)

*No adjustment required.

Содержание GHBVL50

Страница 1: ...tomer service department at 1 877 886 5989 8 00 a m 4 30p m EST Monday Friday or e mail customerservice usaprocom com WARNING IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY A FIRE OR EXPLOS...

Страница 2: ...acement Parts 19 WARNING Read the installation operation instructions before using this appliance IMPORTANT Read instructions and warnings carefully before starting installation Failure to follow thes...

Страница 3: ...rols can be dangerous WARNING Fire burn inhalation and explosion hazard Keep solid combustibles such as building materials paper or cardboard a safe distance away from the heater as recommended by the...

Страница 4: ...hese unit heaters are certified for installation to combustible material as listed in Table 1 Unit Clearances and on unit rating plate Accessibility and service clearances must be observed in addition...

Страница 5: ...ers directing airflow as desired 2 Choose location for mounting brackets 3 Remove and retain three screws along top edge bottom edge when inverted of front of unit 4 Align screw holes on mounting brac...

Страница 6: ...plicable as well as the modifications and imitations listed in figure 3 Seal single wall vent material according to section General Recommendations and Requirements 2 The vent connector shall be 4 102...

Страница 7: ...ing may be troublesome and may cause some staining Avoid windows where steam may cause fogging or ice buildup 5 When horizontally vented minimum clearance for termination from any door window gravity...

Страница 8: ...ll vent material according to the section General Recommendations and Requirements In areas where local authorities having jurisdiction permit a downward slope of maximum 1 4 6mm per foot 305mm is als...

Страница 9: ...rizontal Venting General and Horizontal Venting Residential 2 The vent pipe diameter for horizontal residential installations shall be 4 102mm on 45K Btu hr units and 75K Btu hr units A standard vent...

Страница 10: ...recognized standards lined or relined with suitable materials or replaced with a gas vent or chimney suitable for venting unit heaters The chimney passageway must be checked periodically to ensure tha...

Страница 11: ...11 Electrical Connections...

Страница 12: ...s a precise instrument Please handle it with care Turn off electricity to the appliance before installing or servicing thermostat or any part of the system Do not turn electricity back on until work i...

Страница 13: ...er must supply an external regulator for liquid propane The external regulator is provided by the gas supplier for natural gas The external regulator will reduce incoming gas pressure You must reduce...

Страница 14: ...ment trap in a supply line as shown in Fig 9 Locate sediment trap where it is within reach for cleaning and not likely to freeze Install in the piping system between fuel supply and heater A sediment...

Страница 15: ...Pressure supply piping system by either using compressed air or opening gas supply tank valve 3 Check all joints from gas meter to equipment shutoff valve see Fig 13 Apply mixture of liquid soap and...

Страница 16: ...will snap to OFF See Figure 17 6 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you then smell gas STOP FOLLOW B in the saftey information above If you do not...

Страница 17: ...on control failure When thermostat is placed in continuous fan mode LED will slowly flash High Altitude Adjustments Units may be fired at full input up to 2000 feet 610m above sea level Above 2000 fee...

Страница 18: ...w of gas Gas Pressure Adjustment 1 Check gas line pressure with unit firing at maximum rate A minimum of 7 178mm w c for natural gas or 10 4 264mm w c for LP propane gas should be maintained for prope...

Страница 19: ...procedure is as follows 1 Turn off the manual gas valve 2 Set the thermostat to call for heat 3 System begins normal sequence of operation 4 After approximately 30 seconds pre purge period the LED wil...

Страница 20: ...15 PRESSURE SWITCH TUBE GHBV48306 GHBV48306 1 16 INDUCED DRAFT MOTOR GHBV48320 GHBV48320 1 17 VENT ADAPTER GHBV78321 GHBV78321 1 18 INDUCED DRAFT MOTOR GASKET GHBV48220 GHBV48220 1 19 BACK BRACKET GHB...

Страница 21: ...21 ILLUSTRATED PARTS GHBVN50 GHBVN80...

Страница 22: ...ginal factory replacement parts voids this warranty The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit WHAT IS NOT COVERE...

Отзывы: