background image

                                        6

       WARNING:   

Rework   worksheet,  adding

the  space  of   the  adjoining  unconfined
space.  The  combined   spaces  must   have
enough  fresh air  to supply  all  appliances  in
both  spaces.

If  the actual  Btu/Hr  used  is   less  than   the  maximum   Btu/Hr   the  space  can  support, the   space  is   an
unconfined  space. You  will  need  no  additional  fresh  air  ventilation.

3. Add  the  Btu/Hr of all fuel burning appliances in the space.

     Vent-free heater                                                       Btu/Hr
     Gas water heater*                                                    Btu/Hr
     Gas furnace                                                             Btu/Hr
     Vented gas heater                                                   Btu/Hr
     Gas heater logs                                                       Btu/Hr
     Other gas appliances* +                                          Btu/Hr
    Total                                =                                        Btu/Hr

    *Do  not  include  direct-vent  gas  appliances. Direct-vent  draws  combustion  air  from  the  outdoors  and
       vents to the outdoors.

4. Compare  the  maximum  Btu/Hr  the  space  can  support  with  the  actual amount of Btu/Hr used.

                          

Btu/Hr (maximum the space can support)

                         

Btu/Hr (actual amount of Btu/Hr used)

         

Example

 :  51,200 Btu/Hr(maximum the space can support)

                           56,000 Btu/Hr(actual amount of Btu/Hr used)
The  space  in  the  above  example  is  a  confined  space  because  the  actual  Btu/Hr  used  is  more  than  the
maximum  Btu/Hr  the  space  can  support.
You  must  provide  additional  fresh  air.  Your  options  are  as  follows:
A.  Rework  worksheet, adding  the  space  of  an  adjoining  room. If  the  extra  space  provides  an  unconfined
space, remove  door  to  adjoining  room  or  add  ventilation  grills   between  rooms. 

See  Ventilation  Air  From

Inside  Building (below)

.

B.  Vent  room  directly  to  the  outdoors. See  

Ventilation  Air  From  Outdoors

 (below).

C.  Install  a  lower  Btu/Hr  heater, if  lower  Btu/Hr  size  makes  room  unconfined.

Figure  2 -Ventilation  Air  from  Inside  Building

 Example:
 Gas  water  heater          30,000        Btu/Hr
 Vent-free  heater    +      26,000        Btu/Hr
 Total                         =     56,000        Btu/Hr

This  fresh air  would come  from an adjoining  uncon-
fined space.  When  ventilating  to  an  adjoining uncon-
fined space, you  must  provide  two  permanent  openings:
one within 12

"

 of  the  ceiling  and  one  within 12

"

 of  the

floor on  the  wall  connecting   the  two  spaces (see
options 1 and  2, Figure 2). You  can  also  remove  door
into  adjoining  room (see  option 3, Figure 2). Follow  the

National  Fuel  Gas  Code. NFPA  54/ANSI  Z223.1,  Sec-
tion 5.3,  Air  for  Combustion  and  Ventilation

  for re-

quired size of  ventilation grills or ducts.

Ventilation  Air  From  lnside  Building

Ventilation  Air  From Outdoors

Provide extra fresh air by using ventilation grills or ducts.
You must provide two permanent openings: one within
12

"

 of the ceiling and one within 12

"

 of the floor. Connect

these items directly to the outdoors or spaces open to
the  outdoors. These spaces include attics and crawl
spaces. Follow the 

National Fuel Gas Code, NFPA 54/

ANSI  Z223.1, Section 5.3, Air for Combustion and Ven-
tilation

 for required size of ventilation grills or ducts.

IMPORTANT:

 Do not provide openings for  inlet or outlet

air into attic if attic has a thermostat-controlled power
vent. Heated air entering the attic will activate the power
vent.

Figure  3 -Ventilation  Air  from  Outdoors

6

WARNING:

 If the area in which the heater may be operated is smaller than that defined as an unconfined space

or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the
methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation,
or applicable local codes.

Содержание FBL400RHA Series

Страница 1: ...ting plate This appliance is not convertible for use with other gases CUSTOMER CARE 1 877 866 5989 FBN400RHA Series Remote Control Fireplace FBL400RHA Series Remote Control Fireplace FBN400TYLA Series Thermostat Control Fireplace FBL400TYLA Series Thermostat Control Fireplace Continental Appliance Inc U S Office 5 Musick 4600 Highlands Parkway S E Irvine Suite D E CA 92618 Smyrna GA 30082 WARNING ...

Страница 2: ...and free from combustible materials gasoline and other flammable vapors and liquids 1 This appliance is only for use with the type of gas indicated on the rat ing plate This appliance is not con vertible for use with other gases 2 Do not place Propane LP supply tank s inside any structure Locate Propane LP supply tank s outdoors 3 If you smell gas l Shut off gas supply l Do not try to light any ap...

Страница 3: ...he connection installation testing repair or servicing of equipment that is experienced in such work that is familiar with all pre cautions required and that has com plied with all the requirement of the authorty having jurisdiction 15 Turn off and unplug heater and let cool before servicing Only a qualified service person should service and repair heater 16 Operating heater above elevations 18 To...

Страница 4: ...tal heat applications the water vapor does not creat a problem In most applications the water vapor enhances the low humidity atmosphere experienced during cold weather The following steps will help insure that water vapor does not become a problem 1 Be sure the heater is a sized properly for the application including ample combustion air and circulation air 2 If high humidity is experienced dehum...

Страница 5: ...ATION Determining if You Have a Confined or Unconfined Space Use this worksheet to determine if you have a confined or unconfined space Space Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms 1 Determine the volume of the space length width height Length Width Height cu ft volume of space Example Space size...

Страница 6: ...ure 2 Ventilation Air from Inside Building Example Gas water heater 30 000 Btu Hr Vent free heater 26 000 Btu Hr Total 56 000 Btu Hr This fresh air would come from an adjoining uncon fined space When ventilating to an adjoining uncon fined space you must provide two permanent openings one within 12 of the ceiling and one within 12 of the floor on the wall connecting the two spaces see options 1 an...

Страница 7: ... smoke aromatic candles cleaning fluids oil or kerosene lamps etc in the air exist may discolor walls IMPORTANT Vent free heaters add moisture to the air Although this is beneficial installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture See Air for Combustion and Ventilation pages 5 through 6 CHECK GAS TYPE Use only the type of gas indicated on th...

Страница 8: ...ure for purpose of input adjustment NG Models 5 to 10 5 W C Gas supplier provide external regulator for natural gas INSTALLATION Continued WARNING Never connect heater to private non utility gas wells This gas is commonly known as wellhead gas CAUTION Only use a new black iron or steel pipe Internally tinned copper tubing may be used in certain areas Check you local codes Use pipe of 1 2 diameter ...

Страница 9: ...heater and equipment shutoff valve to gas supply Check reconnected fittings for leaks Pressure Testing Heater Gas Connections 1 Open equipment shutoff valve see Figure 8 Figure 9 Checking Gas Joints CHECKING GAS CON NECTIONS WARNING Test all gas piping and connections for leaks after installing or servicing Correct all leaks immediately INSTALLATION Continued 2 Open gas supply tank valve 3 Make su...

Страница 10: ...all the logs exactly as instructed Do not modify logs Only use logs supplied wall heater IMPORTANT Make sure log does not cover any burner ports see Figure 10 Figure 10 Installing Log Set FIG 1 FIG 2 STEP 1 Install log 1 onto the two slots in the rear plate as shown STEP 2 Install log 2 onto the two slots in the left middle plate Install log 3 onto the two slots in the right middle plate STEP 3 In...

Страница 11: ... Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your hand to push in control knob Never use tools If the the appli ance could not operate don t try to repair it Call a qualified service technician or gas supplier Forced or at tempted re pair may result in a fire or explosion D Do not use this appliance if any part has been under wat...

Страница 12: ...t thirty 30 seconds This will allow air to bleed from the gas system 7 With Control Knob pressed in push ignitor button This will light the pilot If needed keep ignitor button until pilot lights MANUAL OVERRIDE CONTROL SYSTEM OPERATING INSTRUCTIONS 8 Keep Control Knob depressed for ten 10 seconds after lighting pilot If pilot goes out repeat steps 6 7 and 8 9 Turn counterclockwise to ON position D...

Страница 13: ...en disconne ct two wires free to fan 2 Mark or tag each wire removed for its exact reconnection Remove the four screws from the fan when installing reverse the steps above See Figure 20 and Figure 23 Figure 20 Fan WARNING Disconnect power be fore attempting any maintenance or cleaning to reduce the risk of fire elec tric shook or personal injury Turn off heater and let cool before cleaning CLEANIN...

Страница 14: ...k the injector holder located at the end of the burner tube again Remove any large particles of dust dirt lint or pet hair with a soft cloth or vacuum cleaner nozzle 5 Blow air into the primary air holes on the injector holder 6 In case any large clumps of dust have now been pushed into the burner repeat steps 3 and 4 Figure 21 Injector Holder On Outlet Burner Tube Exterior l Use a soft cloth damp...

Страница 15: ...2 25 1 2 Weight lbs Stove 276 276 Shipping 308 308 Mantel A5 Dimensions Inches H W D Heater 44 3 16 46 7 8 16 5 8 44 3 16 46 7 8 16 5 8 Carton 44 7 8 51 20 7 8 44 7 8 51 20 7 8 Weight lbs Stove 265 265 Shipping 295 295 Mantel A Dimensions Inches H W D Heater 45 5 8 50 16 7 8 45 5 8 50 16 7 8 Carton 46 1 2 54 1 2 25 1 2 46 1 2 54 1 2 25 1 2 Weight lbs Stove 276 276 Shipping 308 308 For purposes of ...

Страница 16: ...lot unit Spark at ODS pilot but no ignition 1 Gas supply turned off or equip ment shut off valve closed 2 Air in gas lines when installed 3 Depleted gas supply 4 ODS pilot is clogged 5 Gas regulator setting is not correct 6 Pilot electrude position is not correct 7 Wire is not correct or loosen 8 Gas valve is damage 1 Turn on gas supply or open equip ment shutoff valve 2 Press ON OFF button again ...

Страница 17: ...r name l Your address l Model and serial numbers of your heater l How heater was malfunctioning l Type of gas used propane LP or NG l Purchase date REPLACEMENT PARTS l Warranty card Usually we will ask you to return the defective part to the factory REPLACEMENTPARTS NOTE Use only original replace ment parts This will protect your warranty coverage for parts replaced under warranty PARTS UNDER WARR...

Страница 18: ... ASSEMBLY 1 ND1703X400X4 ODS 1 ND1908X400X4 ODS 1 6 FBB504 ODS INLET TUBE ASSEMBLY 1 1 7 FBB502 INLET TUBE ASSEMBLY 1 1 8 FBB503 OUTLET TUBE ASSEMBLY 1 1 QUALITY KEY NO PART NUMBER DESCRIPTION 5 1 2 3 4 SIT545 T STAT VALVE 1 This list contains replaceable parts used in your heater When ordering parts follow the instructions listed under Replacement Parts on page 17 of this manual 18 ...

Страница 19: ... 4 FB 05A5M SIDE PANEL 1 1 5 FB 03A5M BASE 1 1 6 FB 02A5M UPPER PANEL 1 1 7 FHL001 01 BODY TOP COVER 1 1 8 FHL001 02 BODY BOARDING 1 1 9 FHL008 02 BAFFLE 1 1 10 FHL021 022 02 SIDE REFLECTOR 2 2 11 FHL007 02B FIREBOX FLOOR 1 1 12 FBB102 LOUVER ASSEMBLY 1 1 13 FHL001 03 BODY BOTTOM COVER 1 1 14 FBB104 SCREEN 1 1 15 FHL015 01T T STAT VALVE BRACKET 1 1 16 PF06 YJLF F FAN 1 1 17 FBB501 BURNER 1 1 18 BL...

Страница 20: ...M SIDE PANEL 1 1 5 FB 03AM BASE 1 1 6 FB 02AM UPPER PANEL 1 1 7 FHL001 01 BODY TOP COVER 1 1 8 FHL001 02 BODY BOARDING 1 1 9 FhL008 02 BAFFLE 1 1 10 FhL021 022 02 SIDE REFLECTOR 1 1 11 FhL007 02B FIREBOX FLOOR 1 1 12 FBB102 LOUVER 1 1 13 FHL001 03 BODY BOTTOM COVER 1 1 14 FBB104 SCREEN 1 1 15 FHL015 01T T STAT VALVE BRACKET 1 1 16 PF06 YJLF F BLOWER 1 1 NB40 140H BURNER ASSEMBLY 1 NB40 032H BURNER...

Страница 21: ...GULATOR 1 NRV82FB 9 REGULATOR 1 ND4703X400 RHN ODS 1 ND4908X400 RHN ODS 1 NB40 032H BURNER ASSEMBLY 1 NB40 140H BURNER ASSEMBLY 1 HL036 02 INJECTOR 1 HL036 01 INJECTOR 1 9 FBB320RH OUTLET TUBE ASSEMBLY 1 1 QUALITY KEYNO PART NUMBER DESCRIPTION 8 5 6 7 This list contains replaceable parts used in your heater When ordering parts follow the instructions listed under Replacement Parts on page 17 of th...

Страница 22: ... SIDE PANEL 1 1 6 FhL001 01 BODY TOP COVER 1 1 7 FhL001 02 BODY BOARDING 1 1 8 FhL021 022 02 SIDE REFLECTOR 2 2 9 FhL007 02B FIREBOX FLOOR 1 1 10 FhL001 03 BODY BOTTOM COVER 1 1 11 BL016 01 BLOWER MOUNT PANEL 1 1 12 PF06 YJLF F BLOWER 1 1 13 GCRMA1 CONTROL CABINET ASSEMBLY 1 1 14 GCRTA1 REMOTE 1 1 15 GCRRA1 REMOTE ASSEMBLY 1 1 16 FBB104 SCREEN 1 1 17 FBL015 02HR CONTROL PANEL 1 1 NB40 032H BURNER ...

Страница 23: ......

Отзывы: