Electrical Connection

2 Overview

The unit is ready for operation when connection is made 

to the voltage supply. Interrupt the power supply to turn 

off the pyrometer. To prevent accidental short circuits, 

cable wires not in use should be secured to the supplied 

screw terminals.

Cable color  No. Function

White

1 + 24 V DC power supply (18–30 V DC, power  

consumption M3: max. 6 VA, H3: max. 12 VA)

Brown

2 0 V DC power supply (ground)

LEDs 1,2,3 

(Active digital outputs)

 

Green: Indicates an activated 

digital output 

Sighting:

 Through-lens view finder, laser targeting button or 

connector for color video

LED 4 

(Operating status LED)

 

Orange:  Self-test phase 

 

Green:  Ready to operate

 

Red: Error

Display

 

T: 

Temperature measuring mode

 

– – – –:  Measuring temperature below zero scale temp.

 

OVER: 

Measuring temperature above full scale temp.

4 Parameters

 (adjustment buttons for pyrometer configuration)

Press the button repeatedly to get 

access to all settings sequentially 

(subcategory with >)

For adjustment of the possible 

parameters in the categories

Opens a parameter category or takes 

over a modified parameter value

MEASPARA>

  Measurement parameters

 T90 

Response time t

90

 (min–10 s)

 STMODE 

Storage mode peak picker: OFF, trigger 

 

(TRIG), automatic (AUTO), extern (EXT),  

time clear (TIME)

 CLR 

Clear time settings of storage mode

 

(only if STMODE set to TIME): 1 ms–25 s

 Ԑ1 

Emissivity epsilon (5–120%)

 TR1 

Transmittance (5–100%)

 FF 

Fill factor of spot size (5–100%)

 ZSC 

Zero scale temperature 

 FSC 

Full scale temperature 

 TU 

Temperate unit °C / °F 

OUTPUTS>

 Outputs

 ANALOG>

 

Analog outputs

  A1 

Analog current output 1 (0/4–20 mA)

  A1TST 

Test current analog output 1 

(OFF, 10 mA at 0–20 mA, 12 mA at 4–20 mA)

  A2 

Analog current output 2 (0/4–20 mA)

  A2OUT 

Signal analog output 2: off (OFF), measured 

temperature (TEMP), control output (CTR; only 

devices with  PID controller), device temperature 

(DTMP)

  A2TST 

Test current to analog output 2 

(OFF, 10 mA at 0–20 mA, 12 mA at 4–20 mA)

INTERFACE>

  Serial interface

 RSTYPE 

Interface type RS232 / RS485 (only M3)

 BD 

Baud rate  

RS232: 4.8–115.2 kBd, RS485: 4.8–921.6 kBd

 ADD 

Address (00–97)

 DELAY 

Interface delay (00–20)

MISC>

 

Miscellaneous settings

 LG 

Language (English / Deutsch)

 N.PIN 

Set (new) pin for push button lock

 

(off = no pin request)

 FACT.SET 

Reset the device to the factory setting (no / yes)

Factory Settings

 

Analog output 1

: 4–20 mA, signal of measured temperature

 

Analog output 2

: no temperature output

 

Serial interface

: RS485, baud rate: 115.2 kBd

 

Emissivity 

Ԑ=1 (100%)

 

Response time

 t

90

= min (corresponds M3: <1 ms; H3: <40 µs)

 

Digital inputs / outputs

 

- 1:

 Set to input: switching on / off laser targeting light

 

    (devices with view finder or camera: no function)

 

- 2:

 Set to input: clearing of peak picker storage

 

- 3:

 Set to input: no function

Adjusting the 

Measuring Distance / Focus Distance

In the focus point of the lens (focus distance) the spot size diameter is smallest, outside the focused distance the spot size diameter 

is usually bigger. Precise spot sizes can be found in the complete operating manual under “Spot Size Tables”.

 

The 

laser targeting light

 has its smallest and sharpest picture at the point where the spot size is the smallest.

 

■ View finder and Camera Module:

 The measuring distance is found when the object is in focus.

Manual Focusable Optics

Fiber Optics

Motorized Focus 

Fixed focus optics

 

are mounted  

in the  

specified distance.

1.

2.

3.

1.

2.

3.

1.

2.

3.

Hexagon socket 

1.5 mm

1. Release

2. Adjust

3. Lock (hand- 

    screwed)

A sticker on the optics shows the measurement / focus distance (“a” from front of the lens)