The Electrical Resistivity Measurement Principle

As we have seen above, corrosion is an electro-chemical process. The flow of the ions between the 
anodic and cathodic areas and therefore the rate at which corrosion can occur is affected by the 
resistivity of the concrete. 
The Wenner Probe is used to measure the electrical resistivity of the concrete. A current is applied to 
the two outer probes and the potential difference is measured between the two inner probes.

I

V

a

a

a

Resistivity 

ρ

= 2

π

aV/l [k

cm]

Empirical tests have arrived at the following thresh-
old values which can be used to determine the likeli-
hood of corrosion.

When 

ρ

 

 12 k

cm   

corrosion is unlikely

When 

ρ

 = 8 to 12 k

cm   corrosion is possible

When 

ρ

 

 8 k

cm    

corrosion is fairly certain

The electrical resistivity of the concrete cover layer decreases due to:

• 

increasing concrete water content

• 

increasing concrete porosity

• 

increasing temperature

• 

increasing chloride content

• 

decreasing carbonation depth 

When the electrical resistivity of the concrete is low, the rate of corrosion increases.
When the electrical resisitivity is high, e.g. in case of dry and carbonated concrete, the rate of cor-
rosion decreases.

2.5 

Influence of Rebars on Electrical Resisitivity Measurements

The presence of rebars disturbs electrical resisitivity measurements as they conduct current much 
better than the surrounding concrete. This is particularly the case when the cover depth is less than 
30mm. In order to minimize the effect, none of the electrodes should be placed above a rebar when 
measuring, or if this is unavoidable, then perpendicular to the rebar. 

2.6 

Effect of Electrical Resistivity on Half-cell Potential Measure-

ments

Low electrical resistivity leads to more negative potentials that can be measured on the surface and 
the potential gradients become flatter.
In this case the measurement grid for potential measurements may be coarser, as the risk of unde-
tected anodic areas with flatter gradients becomes lower. However, as the resolution between cor-
roding and passive areas is reduced, this may lead to an overestimation of the actively corroding 
surface area.
High electrical resisitivity leads to more positive potentials that may be measured on the surface and 
potential gradients become steeper. 
In this case the measuring grid must be made finer, in order to be able to locate an anode with a 
very steep gradient. However, the more potentials may be misinterpreted as passive areas when only 
considering the absolute value of the potential.

Содержание canin+

Страница 1: ...canin more than 50 years of know how you can measure Made in Switzerland Operating Instructions Corrosion Analyzing Instrument...

Страница 2: ...robe to the indicating device 8 3 3 Power ON and select the correct operating mode 9 3 4 Functional check of the equipment 10 4 Real Tests Potential Measurements 10 4 1 Planning and preparation 11 4 2...

Страница 3: ...uency 27 6 12 Chipping graph 28 6 13 Annotations 28 7 Measuring the electrical resistivity 29 7 1 Preparing the concrete surface for measurement 29 7 2 Reading the display screen 30 7 3 Measuring with...

Страница 4: ...correct Proceq SA makes no warranties and excludes all liability as to the completeness and or accuracy of the information 1 3 Safety Instructions The equipment is not allowed to be operated by childr...

Страница 5: ...they form hydroxide OH with the generally available water and oxygen This principle creates a potential difference that can be measured by the half cell method The basic idea of the potential field m...

Страница 6: ...ments Electrical resistivity of the concrete cover Measure with the Wenner Probe This topic is dealt with in detail in section 2 4 Oxygen content at the reinforcement With decreasing oxygen concentrat...

Страница 7: ...rate of cor rosion decreases 2 5 Influence of Rebars on Electrical Resisitivity Measurements The presence of rebars disturbs electrical resisitivity measurements as they conduct current much better th...

Страница 8: ...lphate with 100 units by weight of distilled water In order to ensure that the solution remains saturated add an additional teaspoonful of copper sulphate crystals into the electrode The electrode sho...

Страница 9: ...For potential measurements the instrument must be in Corrosion analys ing mode Switch between modes by pressing MENU place the cursor at Wenner Probe press START select OFF for Corrosion Analysing mo...

Страница 10: ...ect measurement on the concrete surface possible Yes No Can the influence from surface coatings be estimated and compensated Yes No Remove the surface coating 4 8 4 9 Pre moisten the surface if requir...

Страница 11: ...y be used For more accessible horizontal vertical or overhead surfaces it is much faster to use the 1 Wheel Electrode For large horizontal surfaces the 4 Wheel Electrode is recommended for the reason...

Страница 12: ...often used for example on the walls and ceiling of underground car parks however this can cause a small shift of the potentials It is always necessary to check whether or not a measurement can be mad...

Страница 13: ...ry The number of pages that are still available for use is shown in the top right hand corner of the measuring screen Fig 5 1 e g 491 P indicates 491 pages are still available The number of pages cont...

Страница 14: ...the measurement it should be possible to see a wet patch when applied on dry con crete If this is not the case then the foam rubber plug should be moistened with water again The simplest way to procee...

Страница 15: ...ista i Note The nozzle 1 mm is fit as standard On dry surfaces the felt hoop should leave a clearly visible trace as you measure Depending on the character of the concrete it may be necessary to incre...

Страница 16: ...Example of a typical distribution If the surface under test has both actively corroding as well as passive rebars then the two states exhibit differing statistical distributions of the potential In t...

Страница 17: ...using a small grid is recommended to deter mine the actual Hotspot local potential minimum 5 General Settings 5 1 Backlight The display has a back light which can be switched on or off by pressing the...

Страница 18: ...U END MENU START MENU END OFF ON END END START Main menu for resistivity measuring Pressing MENU saves the settings and takes you to the next higher menu Pressing END saves the settings and takes you...

Страница 19: ...Pressing MENU saves the settings and takes you to the next higher menu Pressing END saves the settings and takes you to the measuring screen Use the and to select navigate and adjust settings Fig 5 2...

Страница 20: ...alue has stabilized If automatic measuring is not selected then values have to be acquired by pressing the START button In both cases values between 200 and 50mV have to be acquired by pressing the ST...

Страница 21: ...hese graphs can be inserted in an assessment report and serve the corrosion engineer together with results of non destructive and destructive tests like concrete cover depth carbonation depth chloride...

Страница 22: ...Output Fig 5 2 in the Canin display device and press START Click on VistaTransfer button to start the download programme A dialog box appears see Fig 6 2 Select the respective COM port All the object...

Страница 23: ...It may be that the objects from a com plete site were not all measured in the same direction See 4 9 3 ProVista allows this to be corrected Select the correct orientation and press OK again to display...

Страница 24: ...ion Click on Configuration to alter the appearance and the language of the potential map Fig 6 5 Configuration Window The number range to which the colours are assigned can be changed through varying...

Страница 25: ...le button and select the file you wish to add If the file is valid the next screen Fig 6 6 will allow the file to be correctly positioned The new file may be rotated or mirrored to match its orientati...

Страница 26: ...ific value 6 9 Additional Functions Save File to save your changes Print View prints the currently visible section of the potential map respectively chipping graph Print File prints the entire measure...

Страница 27: ...iagram 6 11 Cumulative frequency Fig 6 9 Cumulative frequency diagram Following an evaluation See 4 10 the corrosion engineer can place the 3 cursors in such a way that they represent areas of differe...

Страница 28: ...ture like measured chloride content cracks or other defects can be placed directly in the potential map or the chipping graph The information will be printed and shown in bitmaps By default they are c...

Страница 29: ...mmended that annotations within one file be added at different dimension levels i e zoom levels 7 Measuring the electrical resistivity Fig 7 1 Wenner four point probe with cable and control plate The...

Страница 30: ...same location moving the probe a few mm between each measurement and taking a median from the 5 values The well moistened probe should be pressed lightly against the surface of the concrete until the...

Страница 31: ...f the indicating device In case your PC hardware doesn t support serial ports you can use the USB converter part no 390 00 542 Preparing the PC for the Data Transfer Create directory C PROCEQ Windows...

Страница 32: ...surements 980 pages 240 measurements each organised in up to 71 objects and 5 800 resistivity measurements 24 object files tables 256 measurements each Data Output RS 232 interface with USB adapter Ba...

Страница 33: ...trode cable 1 5m 4 9 ft cable coil 25m 82 ft CANIN ProVista PC software on memory stick bottle with copper sul phate 250g 330 00 205 Canin Configuration with Rod and Wheel Electrodes Basic equipment s...

Страница 34: ...5 Cable clip for telescopic extension 380 02 508 S Foam pad to resistance probe set of 4 pcs 11 Maintenance and Support 11 1 Functional check of the electrodes Correct function can be checked by use o...

Страница 35: ...wooden plug facing upwards 11 4 Functional check of the resistivity probe See section 5 5 Assure that the Device Constant shown on the Indicating Device corresponds to the code engraved on the probe...

Страница 36: ...asia proceq com Proceq Rus LLC Ul Optikov 4 korp 2 lit A Office 412 197374 St Petersburg Russia Phone Fax 7 812 448 35 00 info russia proceq com Proceq Middle East P O Box 8365 SAIF Zone Sharjah Unite...

Отзывы: