background image

Technician Setup

Tech Setup Steps 

Adjustment Options

Default

LCD Will Show

Power supply
Factory-installed jumper. Remove only when installing on 

2-transformer systems.

Typical 1H/1C System: 1 Transformer

Wiring Diagrams

Use either O or B terminals for changeover valve.

Use a small piece of wire (not supplied) to connect W and Y terminals.

Typical 1H/1C Heat Pump System

1.  Press MENU button

2. Press and hold 

TECHNICIAN SETUP

 button for 3 seconds.  This 3 second delay is 

designed so that homeowners do not accidentally access the installer settings.

3. Configure the installer options as desired using the table below.

4. Use the                or               keys to change settings and the NEXT STEP or PREV 

STEP key to move from one step to another. Note: Only press DONE key when you 

want to exit the Technician Setup options.

Wiring

Technician Setup

Wiring Tips

RH & RC Terminals

For single transformer systems, leave the 

jumper wire in place between RH and RC. 

Remove jumper wire for two transformer 

systems.

Heat Pump Systems

If wiring to a heat pump, use a small 

piece of wire (not supplied) to connect 

terminals W and Y.

(With NO AUX or 

Emergency Heat)

C Terminal

The C (common wire) terminal does 

not have to be connected when the 

thermostat is powered by batteries.

Wire Specifications

Use shielded or non-shielded 

18-22 gauge thermostat wire.

Caution: 

Electrical Hazard

All components of the control 

system and the thermostat 

installation must conform to Class 

II circuits per the NEC Code.

Warning:

Installation Tip:

 Do not overtighten terminal block screws, as this 

can damage the terminal block.  A damaged terminal block can 

keep the thermostat from fitting on the subbase correctly or cause 

system operation issues.    

Max Torque = 6in-lbs.

Wiring

If you are replacing a thermostat, 

make note of the terminal 

connections on the thermostat 

that is being replaced.  In some 

cases the wiring connections will 

not be color coded. For example, 

the green wire may not be 

connected to the 

G

 terminal.

Loosen the terminal block 

screws. Insert wires then 

retighten terminal block screws.
Place nonflammable insulation 

into wall opening to prevent 

drafts.

1.

2.

3.

Failure to disconnect the power 

before beginning to install this 

product can cause electrical 

shock or equipment damage.

Terminal Designations

C

O

Heat pump changeover valve 

energized in cooling
Heat pump changeover valve 

energized in heating

W

Heat relay

RH

Transformer power for heating

RC

Transformer power for cooling

G

Fan relay

Y

Compressor relay

B

Common wire from secondary side of 

cooling system transformer 

Set fan operation switch to electric.

Optional 24 VAC common connection when thermostat is used in battery power mode.

RC

Y
C

W

G

RH

COMPRESSOR

RELAY

FAN RELAY

C

R

L2
L1 HOT

COOL CHANGE

OVER VALVE

HEAT CHANGE

OVER VALVE

O
B

This feature allows the installer to 

select the minimum run time for 

the compressor. For example: a 

setting of 4 will force the 

compressor to run for at least 4 

minutes every time the 

compressor turns on, regardless of 

the room temperature.

You can select the minimum 

compressor run time from “off”, 

“3”, “4”, or “5” minutes. If 3,4, 

or 5 is selected, the compressor 

will run for at least the selected 

time before turning off.

0

This feature allows the installer 

to change the calibration of the 

room temperature display. For 

example, if the thermostat reads 

70˚ degrees and you would like it 

to read 72˚ then 2.

Room 

Temperature 

Calibration

You can adjust the room 

temperature display to read 

4˚above or below the factory 

calibrated reading.

Minimum

Compressor 

On Time

0.5

The swing setting often called 

“cycle rate”, “differential” or “

anticipation” is adjustable.  A 

smaller swing setting will cause 

more frequent cycles and a 

larger swing setting will cause 

fewer cycles.

Cooling 

Swing

The cooling swing setting is 

adjustable from 0.2˚ to 2˚.  For 

example: A swing setting of 

0.5˚ will turn the cooling on at 

approximately 0.5˚ above the 

setpoint and turn the cooling off 

at approximately 0.5˚ below the 

setpoint.

0FF

This feature will flash a reminder 

in the display after the elapsed run 

time to remind the user to change 

the filter. A setting of “OFF” will 

disable this feature.

Filter Change

Reminder

You can adjust the filter change 

reminder from OFF to 2000 

hours of runtime in 50 hour 

increments.

SE

SO

The swing setting often called 

“cycle rate”, “differential” or 

“anticipation” is adjustable.  A 

smaller swing setting will cause 

more frequent cycles and a larger 

swing setting will cause fewer 

cycles.

The heating swing setting is 

adjustable from 0.2˚ to 2˚. For 

example: A swing setting of 

0.5˚ will turn the heating on at 

approximately 0.5˚ below the 

setpoint and turn the heating off 

at approximately 0.5˚ above the 

setpoint.

Heating

 Swing

0.4

The compressor short cycle delay 

protects the compressor from 

short cycling. This feature will not 

allow the compressor to be turned 

on for 5 minutes after it was last 

turned off.

Selecting “ON” will not allow 

the compressor to be turned on 

for 5 minutes after the last time 

the compressor was switched 

off. Select “OFF” to remove this 

delay.

Compressor

Short Cycle

Delay

0FF

CO

HE

CO

Tech Setup Steps 

Adjustment Options

Default

LCD Will Show

0N

Keypad lockout allows you to 

configure the thermostat so that 

none or some of the keys do not 

function.

PA= Partial keypad lockout, 

locks all the keys except the

          or          keys. FU= Full 

Keypad lockout, locks out all 

the keys. 

Note:

 Keypad lockout 

instructions on page 12.

Keypad

Lockout

PA

PA

KEY LOCK

This feature allows you to set a 

maximum heat setpoint value. 

The setpoint temperature cannot 

be raised above this valve.

Use the          or           key to select 

the maximum heat setpoint.

Range 44˚F   -  90˚F

Heating

Temperature

Setpoint 

Limit

90

˚

HE

HEAT LIMIT

90 

This feature allows you to set a 

minimum cool setpoint value. 

The setpoint temperature cannot 

be lowered below this value.

Use the          or           key to select 

the minimum cool setpoint.

Range 44˚F   -  90˚F

Cooling

Temperature

Setpoint 

Limit

44

˚

CO

44 

Select F for Fahrenheit read out 

or select C for Celsius read out.

˚F for Fahrenheit   

˚C for Celsiust

F˚ or  C˚

F

˚

74

O

You can select either 12 or 24 

hour clock setting.

12 or 24 

Hour Clock

12 Hour 

Clock

12H

Use the          or           key to select 

12 or 24 hour clock.

RC

Y
C

W

G

RH

COMPRESSOR

RELAY

HEAT RELAY

FAN RELAY

C

R

L2
L1 HOT

0.8

0.8

FILTER

CALIBRATE

MIN COMP

COMP DELAY

COOL SWING

HEAT SWING

COOL LIMIT

CLOCK SET

Отзывы: