Dimensions
The GLC150-BG41-RSFL-24V unit dimensions are as follows.
ALARM
This relay switch remains OFF until the LT unit’s system software
completes its startup routine. During this startup period, this external
circuit must be informed that the LT is not yet operational.
Be sure to design a hold timer circuit that will start operations after
the startup routine is completed, or create an alarm monitoring sys-
tem that will monitor the LT unit’s circuits.
Contact Rating
0.15A, AC125V (Resistance Load)
0.6A, DC24V (Resistance Load)
Operating Time (Set Time at 20
o
C) 4ms or less
Recover Time (Reset Time at 20
o
C) 4ms or less
Minimum switching load
1mA / DC5V
Initial Contact Resistance
100m
Ω
or less
2
General Specifications
Rated Voltage
DC24V
Voltage Supply Range
DC20.4 to DC28
.
8V
Ambient Operating Temperature
0
℃
to 50
℃
Ambient Humidity
20
%
RH to 85
%
RH (no condensation)
Atmospheric Pressure
800hPa to 1114hPa (2000 meter or lower)
Atmosphere
Pollution Degree 2
75.8 [2.98]
6 [0.24]
141.2 [5.56]
207 [8.15]
157 [6.18]
191.2 [7.53]
(Unit:mm [in.] : excluding projections)