 Dimensions

The GLC150-BG41-RSFL-24V unit dimensions are as follows.

ALARM

This relay switch remains OFF until the LT unit’s system software
completes its startup routine. During this startup period, this external
circuit must be informed that the LT is not yet operational.
Be sure to design a hold timer circuit that will start operations after
the startup routine is completed, or create an alarm monitoring sys-
tem that will monitor the LT unit’s circuits.

Contact Rating

0.15A, AC125V (Resistance Load)
0.6A, DC24V (Resistance Load)

Operating Time (Set Time at 20

o

C) 4ms or less

Recover Time (Reset Time at 20

o

C) 4ms or less

Minimum switching load

1mA / DC5V

Initial Contact Resistance

100m

 or less

2

 General Specifications

Rated Voltage

DC24V

Voltage Supply Range

DC20.4 to DC28

8V

Ambient Operating Temperature

0

 to 50

Ambient Humidity

20

RH to 85

RH (no condensation)

Atmospheric Pressure

800hPa to 1114hPa (2000 meter or lower)

Atmosphere

Pollution Degree 2

75.8 [2.98]

6 [0.24]

141.2 [5.56]

207 [8.15]

157 [6.18]

191.2 [7.53]

(Unit:mm [in.] : excluding projections)

Содержание LogiTouch GLC150-BG41-RSFL-24V

Страница 1: ...s load control power turning ON an incorrect output signal or malfunction could cause an accident to occur Be sure to design a program that will ensure the safety of your system in in the event of a...

Страница 2: ...power cord is unplugged from the power supply Be sure to reattach the LogiTouch terminal block s plastic cover after completing any terminal wiring If this cover is not reattached an electric shock c...

Страница 3: ...cident Be sure to secure all wiring terminal screws in place with the designated torque Screws and terminals that become loose can cause a short circuit fire or accident Be sure that metal filings or...

Страница 4: ...st all be in accordance with Class I Division 2 wiring methods Article 501 4 b of the National Electrical Code NFPA 70 or as speci fied in Section 18 152 of the Canadian Electrical Code for units inst...

Страница 5: ...This Guide Option Items sold separately LogiTouch Series User Manual GLC150 MM01 Flex Network Cables Logic Program Developer Software LogiTouch Editor Data Transfer Cable GPW CB02 50m FN CABLE2050 31...

Страница 6: ...cuit I Flex Network Connector J Flex Network LED Operation Mode 1 Controller Operation Mode 2 LED Color OFFLINE STOP Green Constant In Operation RUN Green Constant In Operation STOP Green Flashing In...

Страница 7: ...will monitor the LT unit s circuits Contact Rating 0 15A AC125V Resistance Load 0 6A DC24V Resistance Load Operating Time Set Time at 20 o C 4ms or less Recover Time Reset Time at 20 o C 4ms or less...

Страница 8: ...S 422 19 ERB Enable Receive B RS 422 20 ERB Enable Receive B RS 232C 21 CSA Clear Send A RS 422 22 ERA Enable Receive A RS 422 23 NC No Connection 24 NC No Connection 25 NC No Connection Recommended C...

Страница 9: ...nformation about Flex Network or connectable Flex Network I O units see the Flex Network User Manual 5 Installation Before installing the LogiTouch into a cabinet or panel check that the installation...

Страница 10: ...s show the four 4 fastener insertion slot locations Insert each fastener s hook into the slot and pull it back until the hook catches Insertion Slots Panel Hook Tightening the screws with too much for...

Страница 11: ...unit will result in excess noise and vibration Wherever possible use thick wires max 2 mm2 for power terminals and twist the wire ends before attaching the ring terminals Be sure to use the following...

Страница 12: ...ttaching a wire to the LogiTouch s rear face FG terminal on the Power Input Terminal Block be sure to create an exclusive ground 1 Inside the LogiTouch unit the SG Signal Ground and FG Frame Ground te...

Отзывы: