3

Types of cables 

• This cable cannot be used when connecting the GP3000H to the GP3000H Conversion 

Adapter. 

Connecting and removing this cable 

• Dropping this cable’s connector or hitting it against hard objects could result in 

damage to the connector. 

• Be sure to connect the GP2000H Conversion Adapter first, and connect the 

GP3000H last. Otherwise, the RS-232C/RS-422/RS-485 circuit may fail.

1. Connecting the GP2000H Conversion Adapter 

Attachment

(1) Insert the D-Sub connector of this cable into the 37 pin D-Sub connector of the GP2000H 

Conversion Adapter, and fasten the connector in place using the two screws. Use a 
tightening torque of 0.5N•m.

• Avoid bending this cable excessively and pulling this cable with excessive force. Excessive 

bending and pulling can result in cable disconnection.

Name

Model

Description

GP3000H Soft-type 3 m Cable for 

GP2000H Conversion Adapter 

<RS-232C> (with connector)

GP3000H-

CBLSD232-3M

The cable between the 

GP2000H Series RS-232C 

Conversion Adapter and the 

GP3000H, equipped with 

D-Sub connector.

GP3000H Soft-type 10 m Cable for 

GP2000H Conversion Adapter 

<RS-232C> (with connector)

GP3000H-

CBLSD232-10M

GP3000H Soft-type 3 m Cable for 

GP2000H Conversion Adapter 

<RS-422> (with connector)

GP3000H-

CBLSD422-3M

The cable between the 

GP2000H Series RS-422 

Conversion Adapter and the 

GP3000H, equipped with 

D-Sub connector.

GP3000H Soft-type 10 m Cable for 

GP2000H Conversion Adapter 

<RS-422> (with connector)

GP3000H-

CBLSD422-10M

Содержание GP3000H

Страница 1: ...es or medical life support equipment due to these devices inherent requirements of extremely high levels of safety and reliability When using this cable with transportation vehicles trains cars and ships disaster and crime prevention devices various types of safety equipment non life support related medical devices etc use redundant and or failsafe system designs to ensure reliability and safety P...

Страница 2: ...C Conversion Adapter GP2000H AP232 GP2000H RS 422 Conversion Adapter GP2000H AP422 Mitsubishi PLC A QnA FX Series 2 Port Adapter II GP070 MD11 DC24V RS 232C Cable GP410 IS00 O 1 This cable GP3000H CBLSD232 3M GP3000H CBLSD232 10M GP3000H DC24V RS 232C Cable Prepared by user Host Controller PLC etc Host Controller PLC etc RS 422 Cable Prepared by user This cable GP3000H CBLSD422 3M GP3000H CBLSD422...

Страница 3: ...ning torque of 0 5N m Avoid bending this cable excessively and pulling this cable with excessive force Excessive bending and pulling can result in cable disconnection Name Model Description GP3000H Soft type 3 m Cable for GP2000H Conversion Adapter RS 232C with connector GP3000H CBLSD232 3M The cable between the GP2000H Series RS 232C Conversion Adapter and the GP3000H equipped with D Sub connecto...

Страница 4: ...3 Turn the cable connector lock ring to lock the connector so that the small mark for LOCK on the lock ring is aligned with the small mark on the cable connector Removal 1 Unlock the connector that has been locked in the mounting procedure Turn the lock ring as shown so that the small mark is displaced from the mark Then pull out the cable by holding the cable connector To disconnect the cable be ...

Страница 5: ... RESERVE Not labeled 5 OP C OP 6 OP GND OPG 7 BUZZ OUT BZ 8 DOUT GND DOG 9 EMG0A EM0A Emergency switch 0A Normally Open 2 2 To improve noise resistance be sure to twist each pair of wires close to the terminal block 10 EMG0B EM0B Emergency switch 0B Normally Open 2 11 EMG1A EM1A Emergency switch 1A Normally Closed 2 12 EMG1B EM1B Emergency switch 1B Normally Closed 2 13 EMG2A EM2A Emergency switch...

Страница 6: ... s power supply cord should not be bundled with or kept close to main circuit lines high voltage high current or input output signal lines To improve noise resistance make the power cord as short as possible If the supplied voltage exceeds the GP3000H s range connect a voltage transformer Between the line and the ground be sure to use a low noise power supply If there is an excess amount of noise ...

Страница 7: ...nding wire should have a diameter greater than 2 mm2 Create the connection point as close to the GP3000H as possible and make the wire as short as possible When using a long grounding wire replace the thin wire with a thicker wire and place it in a duct Input Output Signal Line Cautions All GP3000H Input and Output signal lines must be separated from all operating circuit power cables If the opera...

Страница 8: ...oofing standards Pro face s GP3000H Conversion Adapter model AGP3000H ADPCOM 01 and a dedicated cable sold separately are necessary to overcome these restrictions Please refer to Accessories in Chapter 1 Overview in the GP3000H Series Hardware Manual UL c UL Approval The system constructing the following three components does not conform to UL c UL standards GP3000H This cable GP2000H RS 232C RS 4...

Отзывы: